Configuration saving and switching
 
Function parameters
Code
Description
CNF1
Parameter name:
Assignment for 2 configurations
Terminal display:
[2 Configurations]
Logic address:
8021 = 16#1F55
Type:
WORD (listing)
CANopen index:
2032/16
Read/write:
R/WS
INTERBUS index:
5FBC/9C
Factory setting:
0
DeviceNet path:
9C/01/9C
See next page.
CNF2
Parameter name:
Assignment for 3 configurations
Terminal display:
[3 Configurations]
Logic address:
8022 = 16#1F56
Type:
WORD (listing)
CANopen index:
2032/17
Read/write:
R/WS
INTERBUS index:
5FBC/9D
Factory setting:
0
DeviceNet path:
9C/01/9D
See next page.
CNFS
Parameter name:
Active configuration
Terminal display:
[Config. active]
Logic address:
8020 = 16#1F54
Type:
WORD (listing)
CANopen index:
2032/15
Read/write:
R
INTERBUS index:
5FB9/D1
DeviceNet path:
89/01/15
0 = The parameter set switching function is not configured
1 =
(CNF0)
: Configuration no. 0 active
2 =
(CNF1)
: Configuration no. 1 active
3 =
(CNF2)
: Configuration no. 2 active
Value of the control bit assigned by 
[2 Configurations]
 
(CnF1)
0
1
0
1
Value of the control bit assigned by 
[3 Configurations]
 
(CnF2)
0
0
1
1
Value of 
[Config. active]
 
(CnFS)
1
2
3
3
Active configuration
0
1
2
2