Configuration saving and switching
 
Configuration switching by selection
The current configuration can be saved in one of the 3 non-volatile configurations in EEPROM using the "Save configuration" 
(SCS)
parameter. In this case, it is not necessary to assign a function in the control word.
One of the 3 non-volatile configurations in EEPROM can be restored to the current configuration using the "Restore configuration" 
(FCS)
parameter.
Note: Value 64 controls the return to factory settings.
The configuration switching commands are only active if the drive is stopped, and not in "5-Operation enabled" state.
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current 
configuration
(RAM)
Save configuration 
(SCS)
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Write
1
2
3
Display 
terminal
Configuration 0
(EEPROM)
Configuration 1
(EEPROM)
Configuration 2
(EEPROM)
Factory settings
Current 
configuration
(RAM)
Restore configuration
(FCS)
Industrial
HMI
terminal
PLC
Modbus
CANopen
Network
Write
1
2
3
64
[Macro configuration]
(CFG)