Configuration saving and switching
 
66
Function parameters
Code
Description
SCS
Parameter name:
Save configuration
Logic address:
8001 = 16#1F41
Type:
WORD (listing)
CANopen index:
2032/2
Read/write:
R/WS
INTERBUS index:
5FBC/9A
DeviceNet path:
9C/01/9A
0 = No  save
1 = Save to configuration no. 0
2 = Save to configuration no. 1
3 = Save to configuration no. 2
FCS
Parameter name:
Restore configuration
Logic address:
8002 = 16#1F42
Type:
WORD (listing)
CANopen index:
2032/3
Read/write:
R/WS
INTERBUS index:
5FBC/9B
DeviceNet path:
9C/01/9B
0 = No restore
1 = Restore configuration no. 0
2 = Restore configuration no. 1
3 = Restore configuration no. 2
64 = Factory setting
FrY
Parameter name:
Parameter groups
Terminal display:
[PARAMETER GROUP LIST]
Logic address:
3022 = 16#OBCE
Type:
WORD (bit register)
CANopen index:
2000/17
Read/write:
R/WS
INTERBUS index:
5FBC/06
Factory setting:
0
DeviceNet path:
70/01/17
Selection of menus to be loaded
bit 0: = 1: 
[All]
 (ALL)
: All parameters
bit 1: = 1: 
[Drive menu]
 (drM)
: The [1 DRIVE MENU] menu without [1.9 COMMUNICATION] and [1.14 CONTROL 
INSIDE MENU]. In the [7 DISPLAY CONFIG.]
 menu,
 
[Return std name]
 returns to 
[No]
bit 2: = 1: 
[Settings]
 (SEt)
: The [1.3 SETTINGS] menu without the 
[IR compensation]
 (UFr)
[Slip compensation]
 (SLP)
and 
[Mot. therm. current]
 (ItH)
 parameters
bit 3: = 1: 
[Motor param]
 (MOt)
: Motor parameters:
[Rated motor power]
 (nPr)
 - 
[Rated motor volt.]
 (UnS)
 - 
[Rated mot. current]
 (nCr) 
-
 
[Rated motor freq.]
 (FrS) 
-
[Rated motor speed]
 (nSP) 
[Auto tuning]
 (tUn) 
-
 
[Auto tuning state]
 (tUS) 
-
 
[U0]
 (U0) 
to
  
[U5]
 (U5) - 
[F1]
 (F1) 
to
[F5]
 (F5) - 
[V. constant power]
 (UCP) - 
[Freq. Const Power]
 (FCP) - 
[Nominal I sync.]
 (nCrS) - 
[Nom motor 
spdsync]
 (nSPS) - 
[Pole pairs]
 (PPnS) - 
[Syn. EMF constant]
 (PHS) - 
[Autotune L d-axis]
 (LdS) - 
[Autotune L q-
axis]
 (LqS) - 
[Cust. stator R syn]
 (rSAS) - 
[IR compensation]
 (UFr) - 
[Slip compensation]
 (SLP) - 
the motor 
parameters that can be accessed in 
[Expert]
 mode
The following options can only be accessed if 
[Config. Source]
 (FCSI)
 =
 
[Macro-Conf]
 (InI)
:
bit 4: = 1: 
[Comm. menu]
 (COM)
: The [1.9 COMMUNICATION] menu without either 
[Scan. IN1 address]
 (nMA1)
 to 
[Scan. IN8 address]
 (nMA8) 
or
 
[Scan.Out1 address]
 (nCA1)
 to 
[Scan.Out8 address]
 (nCA8)
bit 5: = 1: 
[Control Inside menu]
 (PLC)
: The [1.14 CONTROL INSIDE MENU] menu
bit 6: = 1: 
[Monitor config.]
 (MOn)
: The [6 MONITORING CONFIG.] menu
bit 7: = 1: 
[Display config.]
 (dIS)
: The [7 DISPLAY CONFIG.] menu
bits 8 to 15: Reserved (= 0 or 1)