Chapter 3: Accessing the PM IPDU via the Command Line Interface        15
Arguments
Examples
To set the threshold on PM IPDU number one to 5.6A, enter:
To set the threshold on PM IPDU number two phase Y to 5.6A, enter:
pm>alarm 2 5.6 Y
To read the threshold, enter:
assign
The assign command assigns management of an outlet to a given user. This command is available 
to the admin user only.
Syntax 
assign <outlet_number> <user>
Arguments
Examples
To assign outlet 4, 6, 7 and 8 to user tess, enter:
<IPDU#>
IPDU 
number in a daisy chain
<IPDU_ID>
Identification string previously set by the id command
<threshold>
The current threshold is the maximum allowed current on the power strip
<phase_letter>
Specifies the threshold of a specific phase on the PM42 IPDU. When the 
phase letter is not specified on the PM42 IPDU, the threshold will be set 
to the same value for all three phases.
no argument
Displays alarm status of all PM IPDUs in the daisy chain
pm>alarm 1 5.6
pm>alarm
<outlet_number>
Outlet number, such as “5”, outlet name such as “sunfire”, or group of 
outlets such as “1, 3-5”
<user>
Desired username
pm>assign 4, 6-8 tess