16        Cyclades PM IPDU Installer/Administrator/User Guide
buzzer
The buzzer command displays or changes the buzzer notification status. When set to “on”, a buzzer 
sounds when the current exceeds the threshold. This command is available to the admin user only.
Syntax 
buzzer <on|off|status>
Arguments
Examples
To get the current status of the buzzer notification, enter:
To turn buzzer notification on or off, enter:
current
The current command displays the total current drawn by PM IPDUs and the maximum current the 
unit has drawn (current peak). It may also be used to clear the saved peak current value.
Syntax 
current [<IPDU#>|<IPDU_ID>]|reset
For PM42 IPDU:
current [<IPDU#>|<IPDU_ID> [<phase_letter>]]|reset
on
Enables buzzer
off
Disables buzzer
status
Displays buzzer status
pm>buzzer status
pm>buzzer on
pm>buzzer off