GE 30 Manual De Usuario

Descargar
Página de 88
 
GE
 
OPM_SGS_USM_10K_40K_0US_V010.doc 
60/88 Operating 
Manual 
SG Series 10, 20, 30 & 40 kVA 
7.3.6  Parallel system shutdown (No Load supply) 
 
 
The Load must be disconnected. 
 
 
Initial status: Load supplied from all Inverters
 
 
First operated unit 
All other units of the system 
 
 
1. Press total off button on any one on the Units. 
• 
Load is disconnected from UPS. 
• 
Rectifier and Inverter are shut down and all output and input Contactors will be 
opened. 
• 
LED’s, Rectifier, Inverter and Load are OFF.
 
 
 
First operated unit
 
All other units of the system
 
 
 
2.  Open Q1 (Pos. O) on all Units.
 
 
 
First operated unit
 
All other units of the system
 