Supported System Types
ZL0093-0A
11/2011
SUPPORTED SYSTEM TYPES
The meter has a number of different possible system wiring configurations (see 
Wiring Diagrams). To configure the meter, set the System Type via the User 
Interface or Modbus register 130. The System Type tells the meter which of 
its current and voltage inputs are valid, which are to be ignored, and if neutral 
is connected. Setting the correct System Type prevents unwanted energy 
accumulation on unused inputs, selects the formula to calculate the Theoretical 
Maximum System Power, and determines which phase loss algorithm is to be 
used. The phase loss algorithm is configured as a percent of the Line-to-Line 
System Voltage (except when in System Type 10) and also calculates the 
expected Line to Neutral voltages for system types that  have Neutral (12 & 40).
Values that are not valid in a particular System Type will display as “----” on the 
User Interface or as QNAN in the Modbus registers.
Table 3      
Supported system types
CTs
Voltage Connections
System Type
Phase Loss Measurements
Wiring Diagram
Number 
of wires
Qty
ID
Qty
ID
Type
Modbus 
Register 
130
User 
Interface: 
SETUP>
S SYS
VLL
VLN
Balance
Diagram number
Single-Phase Wiring
2
1
A
2
A, N
L-N
10
1L + 1n
AN
1
2
1
A
2
A, B
L-L
11
2L
AB
2
3
2
A, B
3
A, B, N
L-L with N
12
2L + 1n
AB
AN, BN
AN-BN
3
Three-Phase Wiring
3
3
A, B, 
C
3
A, B, C
Delta
31
3L
AB, BC, 
CA
AB-BC-CA
4
4
3
A, B, 
C
4
A, B, 
C, N
Grounded Wye
40
3L + 1n
AB, BC, 
CA
AN, BN, 
CN
AN-BN-CN & 
AB-BC-CA
5, 6