Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
9
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Wiring
WIRING
       
 
DANGER
   
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•  Apply appropriate personal protective equipment (PPE) and follow safe 
electrical work practices. See NFPA 70E in the USA or applicable local 
codes.
•  This equipment must only be installed and serviced by qualified electrical 
personnel.
•  Turn off all power supplying equipment before working on or inside the 
equipment.
•  Always use a properly rated voltage sensing device to confirm power is 
off.
•  Read, understand, and follow the instructions before installing this 
product.
    Failure to follow these instructions will result in death or serious injury.
 
To avoid distortion, use parallel wires for control power and voltage inputs. 
The following symbols are used in the wiring diagrams on the following pages.
Table 5 
Wiring Symbols
Symbol
Description
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance 
with local requirements. No fuses are included with 
the meter.)
Earth ground
S2
S1
Current Transducer
Potential Transformer
Protection device containing a voltage disconnect 
switch with a fuse or disconnect circuit breaker. The 
protection device must be rated for the available 
short-circuit current at the connection point.
RISK OF EQUIPMENT DAMAGE
•  This product is designed only for use with 1V or 0.33V current 
transducers (CTs).
•  DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS 
PRODUCT.
Failure to follow these instructions can result in overheating and 
permanent equipment damage.
CAUTION