Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
16
Before you begin
Carefully read and follow the safety precautions before working with the meter.
Safety precautions
Installation, wiring, testing and service must be performed in accordance with all local and 
national electrical codes.
Pollution degree
2
Altitude
2000 m CAT III / 3000 m CAT II
For indoor use only
Electromagnetic Compatibility 
3
Electrostatic discharge
IEC 61000-4-2
Immunity to radiated fields
IEC 61000-4-3
Immunity to fast transients
IEC 61000-4-4
Immunity to surge
IEC 61000-4-5
Conducted immunity 150kHz to 80MHz
IEC 61000-4-6
Immunity to magnetic fields
IEC 61000-4-8
Immunity to voltage dips
IEC 61000-4-11
Radiated emissions
FCC part 15, EN 55022 Class B
Conducted emissions
FCC part 15, EN 55022 Class B
Safety
Europe
CE, as per IEC 61010-1 (3rd Edition), IEC 62052-11 
& IEC61557-12 
1
U.S. and Canada
cULus as per UL61010-1 (3rd Edition) 
CAN/CSA-C22.2 No. 61010-1 (3rd Edition)
Measurement category (Voltage and Current inputs)
CAT III up to 400 V L-N / 690 V L-L
Dielectric
As per IEC/UL 61010-1 (3rd Edition)
Protective Class
II, Double insulated for user accessible parts
Communication
RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit), 
JBUS
2-Wire, 9600,19200 or 38400 baud, Parity - Even, 
Odd, None, 1 stop bit if parity Odd or Even, 2 stop 
bits if None; (Optional)
Firmware and language file update
Meter firmware update via the communication ports
Isolation
2.5 kVrms, double insulated
Human Machine Interface
Display type
Monochrome Graphics LCD
Resolution
128 x 128
Backlight
White LED
Viewable area (W x H)
67 x 62.5 mm
Keypad
4-button
Indicator Heartbeat / Comm activity
Green LED
Energy pulse output / Active alarm indication (configurable) Optical, amber LED
Wavelength
590 to 635 nm
Maximum pulse rate
2.5 kHz
1
 
For firmware version 1.1.1 and higher
2
 For 1A nominal CT when I > 0.15A
Tests are conducted as per IEC 61557-12 (IEC 61326-1), 62052-11 and EN50470