Schneider Electric PM5100 Manual De Usuario

Descargar
Página de 96
PowerLogic™ PM5100 series user guide 
Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
19
Meter wiring
For wiring instructions and safety precautions, see the meter installation sheet that was 
shipped with your meter, or download a copy at www.schneider-electric.com.
Wire connections to the meter’s voltage inputs, control power, digital output, and RS-
485 communications are terminated using the supplied pluggable wire connectors.
When wiring the meter’s current inputs, terminate the wire ends with ring or split-ring 
crimp connectors. 
Use the meter installation sheet when wiring the meter.
Serial No.
Description
Specification
Voltage Inputs (V1, V2, V3, VN)
Wire size
: 0.82 - 3.31 mm
2
 (18 - 12 AWG)
Wire strip length
: 0.28 in (7 mm)
Torque
: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type
: M3
Control Power (L1, L2)
Wire size
: 0.82 - 3.31 mm
2
 (18 - 12 AWG)
Wire strip length
: 0.28 in (7 mm)
Torque
: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type
: M3
 Digital Output (D1+, -/C)
Wire size
: 0.33 - 3.31 mm
2
 (22 - 12 AWG)
Wire strip length
: 0.24 in (6 mm)
Torque
: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type
: M2
Current Inputs
(I
1+
, I
1-
, I
2+
, I
2-
, I
3+
, I
3-
)
Wire size
: 0.82 - 3.31 mm
2
 (18 - 12 AWG)
Wire strip length
:0.28 in (7 mm)
Torque
: 0.9 - 1.0 N·m (8.0 - 9.0 in·lb)
Screw driver type
: PH1
Modbus RS-485 (+,-, 
, C)
Wire size
: 0.33 - 3.31 mm
2
 (22 - 12 AWG)
Wire strip length
: 0.24 in (6 mm)
Torque
: 0.5 - 0.6 N·m (4.4 - 5.3 in·lb)
Screw driver type
: M3
RS-485
Modbus
Modbus
RS-485
D1 = Rx+, Tx+
D0 = Rx-, Tx-
0 V
_
+
I
1+
I
1-
I
2+
I
2-
I
3+
I
3-
+
_
UL: CAT III
20-347VLN/35-600VLL 
IEC: CAT III
20-400VLN/35-690VLL
$$120$
9/19//s