PowerLogic™ PM5100 series user guide 
Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
18
Mounting the PM5100
The meter is designed to be mounted inside a 1/4-DIN panel cutout.
1. Inspect the gasket (installed around the perimeter of the front display) and make sure 
it is secured properly and not damaged.
2. Insert the meter through the mounting hole.
3. Line up the tabs of the retainer clips with the slots on either side of the meter. While 
holding the retainers at a slight angle, push the retainers in and forward to position 
them in place. In situations where the spacing between meters is tight, use a flat-head 
screwdriver with a long, narrow shaft to help secure the clips.
4. Push the middle of the clip assembly to lock the retainer in place and secure the 
meter.
92.0 mm
+0.8
-
0.0
92.0
mm
+0.8
-
0.0
CLICK
CLIC