63230-500-225A2
PowerLogic
TM
 Series 800 Power Meter
3/2011
Chapter 3—Operation
15
COMMS (Communications) Setup
NOTE: If you are using PowerLogic software to set up the power meter, it is recommended 
you set up the communications features first.
Refer to Table 3-1 for the meter’s default settings.
The same procedure is used to program the settings for the COMMS, COMM 1, and 
COMM 2 options.
METER Setup
This feature allows the user to configure the CTs, PTs, system frequency, and system 
wiring method.
CTs Setup
Table 3–1: Communications Default Settings
Communications Setting
Default
Protocol
MB.RTU (Modbus RTU)
Address
1
Baud Rate
9600
Parity
Even
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until COMMS (communications) 
is visible.
3. Press COMMS (communications).
4. Select the required protocol: MB.RTU (Modbus 
RTU), Jbus, MB. A.8 (Modbus ASCII 8 bits), 
MB. A.7 (Modbus ASCII 7 bits).
5. Press OK.
6. Enter the ADDR (power meter address).
7. Press OK.
8. Select the BAUD (baud rate).
9. Press OK.
10. Select the parity: EVEN, ODD, or NONE.
11. Press OK.
12. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
13. Press YES to save the changes.
 
,-(
.
PLS
D
110
100
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until METER is visible.
3. Press METER.
4. Press CT.
5. Enter the PRIM (CT primary) number.
6. Press OK.
7. Enter the SEC. (CT secondary) number.
8. Press OK.
9. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
10. Press YES to save the changes.
 
P
LS
D
1101