Chapter 3—Operation
17
ALARM (Alarms) Setup
There is an extensive list of meter error conditions
which can be monitored and cause an alarm.
which can be monitored and cause an alarm.
1. Perform steps 1 through 5 of the SETUP MODE
Access procedure on page 11.
2. Press
###:
until ALARM is visible.
3. Press ALARM.
4. Press
4. Press
<-
or
->
to select the alarm option you
want to edit.
5. Press EDIT.
6. Select to ENABL (enable) or DISAB (disable)
6. Select to ENABL (enable) or DISAB (disable)
the alarm.
7. Press OK.
8. Select the PR (priority): NONE, HIGH, MED, or
8. Select the PR (priority): NONE, HIGH, MED, or
LOW.
9. Press OK.
10. Select how the alarm values are displayed:
10. Select how the alarm values are displayed:
ABSOL (absolute value) or RELAT (percentage
relative to the running average).
relative to the running average).
11. Enter the PU VALUE (pick-up value).
12. Press OK.
13. Enter the PU DELAY (pick-up delay).
14. Press OK.
15. Enter the DO VALUE (drop-out value).
16. Press OK.
17. Enter the DO DELAY (drop-out delay).
18. Press OK.
19. Press
12. Press OK.
13. Enter the PU DELAY (pick-up delay).
14. Press OK.
15. Enter the DO VALUE (drop-out value).
16. Press OK.
17. Enter the DO DELAY (drop-out delay).
18. Press OK.
19. Press
1;
to return to the alarm summary
screen.
20. Press
1;
to return to the SETUP MODE screen.
21. At the SETUP MODE screen, continue
programming additional setup features or
press
press
1;
until you are asked to save changes.
22. Press YES to save the changes.
. .
+
*
*