Diagnostics and Troubleshooting
Drive does not start, no error code displayed
• If the display does not light up, check the power supply to the drive (ground and input phases connection, see page 
• The assignment of the "Fast stop" or "Freewheel" functions will prevent the drive starting if the corresponding logic inputs are not powered
up. The ATV12 then displays 
nSt
 in freewheel stop and 
FSt
 in fast stop, it will display 
rdY
 en freewhell stop. This is normal since
these functions are active at zero so that the drive will be stopped if there is a wire break. Assignment of LI to be checked in 
COnF
/
FULL
/
FUn-
/
Stt-
 menu.
• Make sure that the run command input(s) is activated in accordance with the selected control mode (parameters 
page 
 and 
 page 
, i
COnF
/
FULL
I_O-
menu).
• If the reference channel or command channel is assigned to Modbus, when the power supply is connected, the drive displays "
nSt
"
freewheel and remain in stop mode until the communication bus sends a command.
• In factory setting "RUN" button is inactive. Adjust parameters 
 
 page 
 and 
 page
 to control the drive locally (
COnF
/
FULL
/
CtL-
Fault detection codes that cannot be cleared automatically
The cause of the detected fault must be removed before clearing by turning off and then on. 
SOF
 and 
tnF
 faults can also be cleared remotely by means of a logic input (parameter 
 page 
in 
COnF
/
FULL
/
FLt-
menu).
Code
Name
Possible causes
Remedy
CrF1
Precharge
• Charging relay control fault or 
charging resistor damaged
• Turn the drive off and then back on again
• Check the connections
• Check the stability of the main supply
• Contact your local Schneider Electric 
representative
InFI
Unknown drive rating
• The power card is different from 
the card stored
• Contact your local Schneider Electric 
representative
InF2
Unknown or incompatible power 
board
• The power card is incompatible 
with the control card
• Contact your local Schneider Electric 
representative
InF3
Internal serial link
• Communication interruption 
between the internal cards
• Contact your local Schneider Electric 
representative
InF4
Invalid industrialization zone
• Inconsistent internal data
• Contact your local Schneider Electric 
representative
InF9
Current measurement circuit
• Current measurement is not 
correct due to hardware circuit
• Contact your local Schneider Electric 
representative
----
Problem of application Firmware
• Invalid application firmware 
update using the Multi-Loader tool
• Flash again the application firmware of the 
product
InFb
Internal thermal sensor detected 
fault
• The drive temperature sensor is 
not operating correctly
• The drive is in short circuit or open
• Contact your local Schneider Electric 
representative
InFE
Internal CPU
• Internal microprocessor
• Turn the drive off and then back on again
• Contact local Schneider Electric 
representative