Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
BBV28581  05/2010
109
Fault detection codes that can be cleared with the automatic restart function, after 
the cause has disappeared
These faults can also be cleared by turning on and off or by means of a logic input (parameter 
page
).
Code
Name
Possible causes
Remedy
LFFI
AI current lost fault
Detection if: 
• Analog input AI1 is configured as 
current 
 pag
 is greater 
than 3 mA
• Analog input current is lower than 
2 mA 
• Check the terminal connection
ObF
Overbraking
• Braking too sudden or driving load 
too high
• Increase the deceleration time
• Install a module unit with a braking resistor if necessary
• Check the line supply voltage, to be sure that it is under 
the maximum acceptable (20% over maximum line supply 
during run status)
OHF
Drive overheat
• Drive temperature too high
• Check the motor load, the drive ventilation and the 
ambient temperature. Wait for the drive to cool down 
before restarting. See Mounting and temperature 
conditions pa
ge 
OLC
Process overload
• Process overload 
• Check the process and the parameters of the drive to be 
in phase
OLF
Motor overload
• Triggered by excessive motor 
current
• Check the setting of the motor thermal protection, check 
the motor load.
OPF1
1 output phase loss
• Loss of one phase at drive output
• Check the connections from the drive to the motor
• In case of using downstream contactor, check the right 
connection, cable and contactor
OPF2
3 output phase loss
• Motor not connected
•  Motor power too low, below 6% of 
the drive nominal current
• Output contactor open
• Instantaneous instability in the 
motor current
• Check the connections from the drive to the motor
• Test on a low power motor or without a motor: In factory 
settings mode, motor phase loss detection is active 
YES
. To 
check the drive in a test or maintenance environment, 
without having to use a motor with the same rating as the 
drive, deactivate motor phase loss detection 
nO
• Check and optimize the following parameters: 
 page 
 page 
 
an
page 
 and perform an 
 page 
OSF
Main overvoltage
• Line voltage too high:
- At drive power on only, the 
supply is 10% over the 
maximum acceptable voltage 
level
- Power with no run order, 20% 
over the maximum line supply
• Disturbed line supply
• Check the line voltage