Schneider Electric Altivar 12 Manual De Usuario
BBV28581 05/2010
111
Faults codes that will be cleared as soon as their causes disappear
page
).
(1) When the CFI is present in the past fault menu, it means the configuration has been interrupted or is not fully finished.
HMI block changed
When an HMI block is replaced by an HMI block configured on a drive with a different rating, the drive locks in Incorrect configuration
CFF
fault mode on power-up. If the card has been deliberately changed, the fault can be cleared by returning to factory setting.
Code
Name
Possible causes
Remedy
CFF
Incorrect
configuration
configuration
• HMI block replaced by an HMI
block configured on a drive with a
different rating
different rating
• The current configuration of
customer parameters is
inconsistent
inconsistent
• Return to factory settings or retrieve the backup
configuration, if it is valid.
• If the fault remains after reverting to the factory settings,
contact your local Schneider Electric representative
CFI
(1)
Invalid configuration
• Invalid configuration
The configuration loaded in the
drive via the bus or communication
network is inconsistent. The
configuration upload has been
interrupted or is not fully finished.
drive via the bus or communication
network is inconsistent. The
configuration upload has been
interrupted or is not fully finished.
• Check the configuration loaded previously.
• Load a compatible configuration
• Load a compatible configuration
CFI2
Download invalid
configuration
configuration
• Interruption of download operation
with Loader or SoMove
• Check connection with Loader or SoMove.
• To reset the default re-start the download operation or
• To reset the default re-start the download operation or
restore the factory setting
USF
Undervoltage
• Line supply too low
• Transient voltage dip
• Transient voltage dip
• Check the voltage and the parameters of
Undervoltage
Phase Loss Menu
USb-
page