Faults codes that will be cleared as soon as their causes disappear
The USF fault can be cleared remotely by means of a logic input (parameter 
 pag
).
(1) When the CFI is present in the past fault menu, it means the configuration has been interrupted or is not fully finished.
HMI block changed
When an HMI block is replaced by an HMI block configured on a drive with a different rating, the drive locks in Incorrect configuration 
CFF
fault mode on power-up. If the card has been deliberately changed, the fault can be cleared by returning to factory setting.
Code
Name
Possible causes
Remedy
CFF
Incorrect 
configuration
• HMI block replaced by an HMI 
block configured on a drive with a 
different rating
• The current configuration of 
customer parameters is 
inconsistent
• Return to factory settings or retrieve the backup 
configuration, if it is valid.
• If the fault remains after reverting to the factory settings, 
contact your local Schneider Electric representative
CFI
(1)
Invalid configuration
• Invalid configuration
The configuration loaded in the 
drive via the bus or communication 
network is inconsistent. The 
configuration upload has been 
interrupted or is not fully finished.
• Check the configuration loaded previously.
• Load a compatible configuration
CFI2
Download invalid 
configuration
• Interruption of download operation 
with Loader or SoMove
• Check connection with Loader or SoMove.
• To reset the default re-start the download operation or 
restore the factory setting
USF
Undervoltage
• Line supply too low
• Transient voltage dip
• Check the voltage and the parameters of 
Undervoltage 
Phase Loss Menu 
USb-