Schneider Electric Altivar 12 Manual De Usuario
110
BBV28581 05/2010
Fault detection codes that can be cleared with the automatic restart function, after
the cause has disappeared (continued)
the cause has disappeared (continued)
Code
Name
Possible causes
Remedy
PHF
Input phase loss
• Drive incorrectly supplied or a fuse
blown
• Failure of one phase
• 3-phase ATV12 used on a single-
• 3-phase ATV12 used on a single-
phase line supply
• Unbalanced load
• This protection only operates with
• This protection only operates with
the drive on load
• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by setting
• Use a 3-phase line supply.
• Disable the fault by setting
Input Phase loss detection
page
nO
.
SCF5
Load short circuit
• Short-circuit at drive output
• Short circuit detection at the run
• Short circuit detection at the run
order or DC injection order if
parameter
parameter
page
is set to
YES
• Check the cables connecting the drive to the motor, and
the motor’s insulation
SLF1
Modbus
communication
communication
• Interruption in communication on
the Modbus network
• Check the connections of communication bus.
• Check the time-out (
• Check the time-out (
page
)
• Refer to the Modbus user manual
SLF2
SoMove
communication
communication
• Communication interruption with
SoMove
• Check the SoMove connecting cable.
• Check the time-out
• Check the time-out
SLF3
HMI communication
• Communication interruption with
the external display terminal
• Check the terminal connection
SPIF
PI Feedback detected
fault
fault
• PID feedback below lower limit
• Check the PID function feedback
• Check the PI feedback supervision threshold
• Check the PI feedback supervision threshold
LPI
and
time delay
tPI
, page
ULF
Process underload
fault
fault
• Process underload
• Motor current below the
• Motor current below the
during a
period set by
parameter page
to protect the
application.
• Check the process and the parameters of the drive to be
in phase
tJF
IGBT overheat
• Drive overheated
• IGBT internal temperature is too
• IGBT internal temperature is too
high according to ambient
temperature and load
temperature and load
• Check the size of the load/motor/drive.
• Reduce the
• Reduce the
.
• Wait for the drive to cool before restarting