Fault detection codes that can be cleared with the automatic restart function, after 
the cause has disappeared (continued)
Code
Name
Possible causes
Remedy
PHF
Input phase loss
• Drive incorrectly supplied or a fuse 
blown
• Failure of one phase
• 3-phase ATV12 used on a single-
phase line supply
• Unbalanced load
• This protection only operates with 
the drive on load
• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by settin
 page 
nO
.
SCF5
Load short circuit
• Short-circuit at drive output
• Short circuit detection at the run 
order or DC injection order if 
parameter
 page 
 is set to 
YES
• Check the cables connecting the drive to the motor, and 
the motor’s insulation
SLF1
Modbus 
communication
• Interruption in communication on 
the Modbus network
• Check the connections of communication bus.
• Check the time-out (
page 
)
• Refer to the Modbus user manual
SLF2
SoMove 
communication
• Communication interruption with 
SoMove
• Check the SoMove connecting cable.
• Check the time-out
SLF3
HMI communication
• Communication interruption with 
the external display terminal
• Check the terminal connection
SPIF
PI Feedback detected 
fault
• PID feedback below lower limit
• Check the PID function feedback
• Check the PI feedback supervision threshold 
LPI
 and 
time delay 
tPI
, page 
ULF
Process underload 
fault
• Process underload
• Motor current below the 
 parameter page 
 during a 
period set by 
 
 
parameter page 
 to protect the 
application.
• Check the process and the parameters of the drive to be 
in phase
tJF
IGBT overheat
• Drive overheated
• IGBT internal temperature is too 
high according to ambient 
temperature and load
• Check the size of the load/motor/drive.
• Reduce th
.
• Wait for the drive to cool before restarting