Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
30
BBV28581  05/2010
Factory configuration
Drive factory settings
The Altivar 12 is factory-set for the most common operating conditions (motor rating according to drive rating):
• Display: drive ready (
rdY
) motor stopped or motor frequency reference while running
• Automatic adaptation of the deceleration ramp in the event of overvoltage on braking.
• No automatic restarting after a detected fault is cleared
• Logic inputs:
- LI1: forward (2-wire transitional control)
- LI2, LI3, LI4: no assignment
• Logic output: LO1: no assignment
• Analog input: AI1 (0 to + 5 V) speed reference
• Relay R1: the contact opens in the event of a detected fault (or drive off)
• Analog output AO1: no assignment
If the above values are compatible with the application, the drive can be used without changing the settings.
Drive factory wiring diagram
(1) R1 relay contacts, for remote indication of the drive status.
(2) Internal + 24 V 
c
. If an external source is used (+ 30 V 
c
 maximum), connect the 0 V of the source to the COM terminal, and do not
use the + 24 V 
c
 terminal on the drive.
(3) Reference potentiometer SZ1RV1202 (2.2 k
Ω
) or similar (10 k
Ω  
maximum).
(4) Forward
Code
Description
Value
page
50 Hz
230 V
3 seconds
3 seconds
0 Hz
50 Hz
Standard U/F law
100%
Ith
equal to nominal motor current (value determined by drive rating)
0.7 x nominal drive current, for 0.5 seconds.
4 kHz
U/T1
V/T2
W/T3
P
A
 / +
COM
AI1
+5V
AO1
U1
W1
V1
M
 3 a
LI1
LO+
LO-
COM
R1B
R1C
LI2
LI3
LI4
+24 V
PC / -
R1A
R/L1
S/L2
T/L3
(1)
(3)
(2)
(4)
a
c
b
ATV12
pppp
M3
3-phase 
motor
Source