Basic functions
Status relay, unlocking
The R1 status relay is energized when the drive power is applied with no fault detected. It de-energizes in the event of a detected fault or
when the drive power is removed.
The drive is reset after a detected fault:
• by switching off the drive until the display disappears completely, then switching on again
• automatically in the cases described in the "automatic restart" function, 
FLt-
 menu, 
YES
• via a logic input when this input is assigned to the "drive reset" function, 
FLt-
 menu, 
 
 page 
 set to L
p
H.
Drive thermal detection
Thermal detection is provided by a built-in PTC probe in the power module.
Drive ventilation
Ratings up to 0.75 kW (1 HP) do not include a fan. The fan runs only when the drive thermal state requires ventilation.
Motor thermal detection
Function:
Thermal detection by calculating the I
2
t.
Note: The motor thermal state memory returns to zero when the drive power is cycled if 
 pag
is not set to 
YES
.
CAUTION
RISK OF DAMAGE TO THE MOTOR
The use of external overload protection is required under the following conditions:
• Repowering up the product since there is no motor thermal state memory.
• Running multiple motors
• Running motors rated at less than 20% of the nominal drive current
• Using motor switching
Failure to follow these instructions can result in equipment damage.
CAUTION
MOTOR OVERHEATING
• This drive does not provide direct thermal protection for the motor.
• Use of a thermal sensor in the motor may be required for protection at all speeds or loading conditions.
• Consult the motor manufacturer for the thermal capability of the motor when operated over the desired speed range
Failure to follow these instructions can result in equipment damage.