B-04: Set Battery Capacity 
 
z  This setting controls battery charging amperages and other settings. The factory 
setting for CAPACITY is 1000 amp hours for PM-SCC-50AM, 1600 amp hours 
for PM-SCC-80AM, 800 amp hours for PM-SCC-40AMW and 1600 amp hours 
for PM-SCC-80AMW. 
z  At full output capacity a PM-SCC-80AM can deliver 80 amps to a battery, this 
amount of amperage (current) is equal to the C/10 (capacity divided by ten) rate 
of a 1600 amp hour battery and, as such meets most manufacturers 
recommendations for minimum PV charging capacity. 
z  In applications with battery banks under 1600 amp hours it is recommended to 
lower the Maximum Charge Rate setting from the default 80 amps to the C10 
rate of the battery bank. 
 
 
B-05: BAT. MAX Charge Amps 
 
z  Use Constant B-05 to allow the installer to limit the maximum charge amps 
allowed to the batteries. The factory setting is 80 amps (PM-SCC-80AM).   
 
B-06: Set Absorption Volts 
 
z  Use Constant B-06 to adjust the Absorption voltages. The default values are 
based on the battery type and capacity selected. It is not advisable to change 
default settings unless advised by the battery manufacturer or supplier. 
 
Battery Type
Absorption Volts 
Range 
Factory 
Setting 
FLOODED 13.9V~15.2V 
14.6V 
AGM 13.7V~15.1V 14.1V 
GEL 13.6V~15.1V 14.1V 
※  The above values are based on 12V system. The values x 2 are for 24V 
system; the values x 3 are for 36V system and the values x 4 are for 48V 
system.  
 
z  Premium MPPT Series will charge at the Absorption voltage and at the length of 
time before switching to float mode. 
 
 
5-6