Puls UB10.241 UPS Guia De Especificaciones
UB10.241
U–Series
24V, 10A, DC-UPS
18. E
NVIRONMENT
Operational temperature
-25°C to +70°C (-13° to +158°F)
For the DC-UPS control unit.
Keep battery in a cooler environment!
+60°C to +70°C (+140°F to +158°F),
Derating
0.43A/°C
normal mode see Fig. 18-1
+60°C to +70°C (+140°F to +158°F),
+60°C to +70°C (+140°F to +158°F),
0.25A/°C
buffer mode see Fig. 18-2
Storage temperature
-40 to +85°C (-40° to +185°F)
Storage and transportation, except battery
Humidity
5 to 95% r.H.
IEC 60068-2-30
Do not energize while condensation is present
Do not energize while condensation is present
Vibration sinusoidal
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
IEC 60068-2-6
Shock
30g 6ms, 20g 11ms
IEC 60068-2-27
Altitude
0 to 6000m
Approvals apply only up to 2000m
Over-voltage category
III
EN 50178
II
EN 50178 above 2000m altitude
16/23
Degree of pollution
2
EN 50178, not conductive
Fig. 18-1 Output current vs. ambient temperature
Fig. 18-2 Output current vs. ambient temperature
Allowable Output
Current in Normal Mode
Current in Normal Mode
0
-25
0
20
40
70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
Allowable Output
Current in Buffer Mode
Current in Buffer Mode
0
-25
0
20
40
70°C
2.5
5
7.5
10
12.5
15A
continuous
60
Ambient Temperature
for typ. 5s
The ambient temperature is defined 2cm below the unit.
19. P
ROTECTION
F
EATURES
Output
protection
Electronically protected against overload, no-load and short-circuits
Output over-voltage protection
in buffer mode
typ. 32Vdc
max. 35Vdc
max. 35Vdc
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.
Degree of protection
IP20
EN/IEC 60529
Penetration protection
> 3.5mm
E.g. screws, small parts
Reverse battery polarity protection
yes
Max. –35Vdc;
Wrong battery voltage protection
yes
Max. +35Vdc (e.g. 24V battery instead of 12V battery)
Battery deep discharge protection
yes
The limit is battery current dependent
Over temperature protection
yes
Output shut-down with automatic restart
Input
over-voltage
protection
yes
Max. 35Vdc, no harm or defect of the unit
Internal
input
fuse
25A,
blade type
No user accessible part, no service part
June. 2010 / Rev. 1.3 DS-UB10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany