RELAY STATES IN A NORMAL (NON-INTRUSION ) 
MODE 
3.5 
Route power and alarm cable through the cable clamp located on the bottom of the box 
(Figure 3-5, Item 1) and connect wires as shown in Figure 3-6. 
 
 
Figure 3-5 Interface Box Wiring  
 
 
 
 
 
 
 
 
 
 
          Figure 3-6 Wiring Schematic 
 
The Form-C relay contacts are brought out to the  
Interface connection block as individual, independent 
dry contacts. 
 
Absolute maximum rating for these contacts are: 
16 Volts and 100 milliamperes maximum 
Operation beyond these ratings may cause  
permanent damage to the sensor. 
 
The contacts are protected with a self resetting PTC 
fuse in the COM line, which may have an initial  
resistance of up to 2 ohms (at 22
o
 C). 
 
 
 
 
3.6 
After wires have been connected, tighten cable clamp (Figure 3-5, Item 1) securely to 
hold cable in place 
 
3.7 
Close interface box cover and install screws and screw cover tabs. 
1
1
2
3
4
9 10 11 12 13 14 15 SH
TERMINAL 
 
       SIGNAL NAME 
 
ALARM N.O. 
ALARM COM 
ALARM N.C. 
FAULT N.O. 
FAULT COM 
FAULT N.C. 
TAMPER N.O. 
TAMPER COM 
TAMPER N.C. 
10 
SELF TEST (1) 
11 
SELF TEST (2) 
12 
 
13 
+12V POWER 
14 
 12V RTN  
15 
CHASSIS GROUND
SH   
 
          
SENSOR STATE    CONTACT STATE          DIAGRAM 
INTRUSION 
(ALARM) 
 
 
 
 
TAMPER 
 
 
 
 
 
FAULT 
 
Relay contacts close 
when in ALARM 
state 
 
 
 
Relay contacts are  
closed when in non- 
tamper state 
 
 
 
Relay contacts close  
When in fault state 
N. C. 
 
COM 
 
N.O 
N. C. 
 
COM 
 
N.O 
N.C 
 
COM 
 
N.O