Spec
Recommendation
Capacitance (conductor to
conductor)
<20 pF/ft.
Characteristic Impedance
100 – 120 ohms
Nominal DC resistance
<100 ohms/1000 ft.
Wire gauge
24 AWG stranded
Conductors/Shielding
>2 pair (shielded
optional)
It is often hard to quantify if shielded cable is required in an application or not.
Since the added cost of shielded cable is usually minimal it is worth installing the
first time.
The total length of the communication cable (adding up all of the segments of
the run) must not exceed 4000 ft (1200 m) as outlined in the specification for RS-
485 (see reference 3).
Although the RS-485 specification calls out a maximum cable length of 1200
meters and a maximum baud rate well above that of the Veri-Series reader, a
more conservative system should be configured for no more than 1000 meters
and running at a baud rate of 9600 bits per second.  After the network is
configured and is running in a stable manner, the baud rate can be increased if
faster network communications are desired.
Figure 10:  Category 5 cable for RS-485/Ethernet Communications
Drops (down leads) to equipment are not recommended, but if required, should
not exceed 10 feet and should use the same cable recommended above.
Ethernet Cable Specification
Ethernet cables should generally be shielded Category 5 or better.  The V-Station
supports only 10Base-T Ethernet.  Therefore, it only makes sense to use cable for
Table 7:  Recommended Cable Characteristics