iComSL
 
Series Universal Communicator Installation and Programming Guide 
Digital Monitoring Products
5
applIcatIons
3.3 
Zone 4 Bell Connection
Zone 4 (Z4+ and Z4-) can be connected to the control panel bell output. This zone detects an alarm condition
on the control panel by monitoring the voltage and cadence timing of the bell output. See Zone 4 Bell Cadence
Information in the Appendix for cadence timing. To enable alarm detection operation, Zone 4 Bell Connection
must be programmed as Zone Type (A2) in Zone Information programming. The type of Cadence sent to the
iComSL Communicator, the Zone Number, and type of message sent to the SCS-1R or SCS-VR receiver are listed
below:
BELL CADENCE 
ZONE NUMBER 
TYPE OF MESSAGE
 
Steady 
ZONE 4 
BURGLARY
  Pulse or Temporal 3 
ZONE 5 
FIRE
 
Temporal 4 
ZONE 6 
EMERGENCY OR
 
 
 
CARBON MONOXIDE
Note: Zone 5 and 6 are automatically generated by the iComSL, using Zone 4’s Zone name to send to the Central
Station. Zones 5 and 6 cannot be preprogrammed in Zone Information.
Note: CID Dialer Connection cannot be used when using Zone 4 Bell Connection.
Use 18-22 AWG for 
Power Supply 
connection
Z4 
+
Z4 
-
 DMP Panel 
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for 
Power Supply 
connection
Z4 
+
Z4 
-
 ADEMCO Panel 
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for 
Power Supply 
connection
Z4 
+
Z4 
-
 NAPCO Panel 
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
Use 18-22 AWG for 
Power Supply 
connection
Z4 
-
 DSC Panel 
MODEL iComSL
PROG
+12
G
Z1
Z2
Z4-
Z4+
G
Z3
R
T
O2
O1
R
B
J8
J9
S3
12 Vdc Aux. Output
+
-
BELL -
12 Vdc BELL +
10k ohm
1k ohm
1k ohm
1k ohm
1k ohm
1k ohm
2.2k 
ohm
Program Zone 4
DO - Alarm
AO - Alarm
Voltages above 1.4 Vdc 
are considered Alarm
Voltages above 1.4 Vdc 
are considered Alarm
Voltages above 1.4 Vdc 
are considered Alarm
Voltages below 0.7 Vdc 
are considered Alarm
Figure 10: Zone 4 Bell Connection