iComSL
 
Series Universal Communicator Installation and Programming Guide 
Digital Monitoring Products
1
IntroductIon
iComSL™ Series Universal Alarm Communicator
Description
The iComSL™ Series Alarm Communicator provides a fully supervised alarm communication path for any burglary
or residential fire control panel. The iComSL Series can be connected to a control panel’s dialer output and
used to capture Contact ID messages
based on SIA DC-05-1999.09-DCS. The iComSLC has a built-in ethernet
port to connect to a network and send messages to DMP Model SCS-1R or SCS-VR Central Station Receivers.
The communicator also provides four input zones and two open-collector outputs for connection to burglary or 
residential fire control panel outputs and zones. The iComSL Series Communicator Zone 4 allows a connection
to the bell output of an existing burglary control panel. The communicator operates in a variety of applications: 
CID Dialer Connection, Zones 1-4 Input Connections, or Zone 4 Bell Connection (See Applications on page 5). The
iComSLCZ™ Alarm Communicator includes an onboard Z-Wave controller for home automation applications.
What is Included
The iComSL Series Universal Alarm Communicator includes the following:
•  PCB with Enclosure
•  Hardware Pack
System Components
1.1 
Terminals (J9)
Power Connection Terminals
Power is provided from the Nominal 12 Vdc auxiliary output of the burglary control panel.
OBSERVE POLARITY (See Figure 1 and Backlit Logo)
Using 18 - 22 AWG wire, connect the communicator terminal +12 to the positive terminal on the control panel 
auxiliary output.
Connect the communicator terminal G (Ground) to the negative terminal on the control panel auxiliary output.
Control Panel Standby Power
During a power outage, the iComSL draws power from the control panel’s backup battery. The iComSL must be
included in the standby battery calculations for the control panel.
Zones 1-4
Terminals Z1 to Z3, G (Ground), Z4+ and Z4- provide four zones to connect to individual relay outputs on
the control panel. Zone 4 (Z4+ and Z4-) can be connected to the control panel bell output. See Zone 4 Bell
Connection.
Figure 1: iComSL Series Communicator