Digital Monitoring Products Inc PC0179 Manual De Usuario

Descargar
Página de 38
Digital Monitoring Products 
iComSL
 
Series Universal Communicator Installation and Programming Guide
2
system components
Open-Collector Outputs
The two outputs, terminals O1 and O2 (see Figure 1), can be programmed to indicate the activity of the zones
or conditions occurring on the system. Open-Collector outputs do not provide a voltage but instead switch-to-
ground the voltage from another source. Maximum voltage is 30Vdc @ 50 mA. The outputs can respond to any of
the conditions listed below:
1)  Activation by zone condition: Steady, Pulse, Momentary, or Follow
2)  Communication
3)  Armed area annunciation
4)  Remote Arming Output
Dialer Connection
Directly connect the telco phone line (tip and ring) from the control panel to the iComSL Series Universal
Communicator terminal R (Ring) and one into T (Tip) (See CID Dialer Connection).
1.2 
Programming Connection
A 4-pin header (PROG) is provided to connect a keypad when using a DMP
Model 330 Programming Cable. This provides a quick and easy connection
for programming the iComSL
 Series Universal Alarm Communicator. After
programming is complete, remove the keypad.
1.4 Tamper
The tamper button is pressed when the cover of the iComSL Series
Communicator is secured onto the enclosure. When the cover is removed, the
communicator sends a Tamper Trouble message to the Central Station.
1.5 
Reset Button
The Reset button is located on the right side of the circuit board and is used to 
reset the communicator microprocessor. After resetting the communicator, begin 
programming within 30 minutes. If you wait longer than 30 minutes, reset the
communicator again.
1.6 
Load Button
The iComSL Series Universal Alarm Communicator software can be updated
via the programming (PROG) header. To update the communicator with a new
software version, complete the following steps at the protected premise:
1.   Connect a DMP 399 Cable from the Programming Header to the serial port of
your PC operating Remote Link and containing the communicator RU file.
2.   Start Remote Link and create or open the account that matches the
communicator to be updated.
3.   Set the Connection Information Type to Direct with a baud rate of 38400 and
choose the appropriate COM port.
4.   Select Panel>Remote Update, then select the correct RU file for the
communicator.
5.  Press and hold the LOAD button, then press and release the RESET button.
6.  Release the LOAD button and click <Update> in Remote Link.
7.   After the software update is completed, remove the 399 cable and press the RESET button to resume normal
operation.
1.7 
Backlit Logo
The backlit logo indicates the Power and Armed status of the communicator. Depending on the operation, the
LED displays in Red or Green as listed in the table. The LED indicates the status of the system battery and
primary power.
Color and Activity
Operation
Green Steady
Communicator Disarmed, Primary Power OK, Battery OK
Green Blinking
Communicator Disarmed, Primary Power OK, Battery Fault
No Light
Communicator Disarmed, Primary Power Fault, Battery OK
Red Steady
Communicator Armed, Primary Power OK, Battery OK
Red/Green Alternate
Communicator Armed, Primary Power OK, Battery Fault
Red Blinking
Communicator Armed, Primary Power Fault, Battery OK
R
B
J8
J1
RESET
LOAD
S1
S2
S3 J9
Figure 2: PROG Port Location
R
B
J8
J1
RESET
LOAD
S1
S2
S3 J9
Figure 3: Tamper Location
R
B
J8
J1
RESET
LOAD
S1
S2
S3 J9
Figure 4: Reset and Load 
Button Location