CleanAlert LLC FS-242 Manual De Usuario
5
8. Wait for approximately 15 seconds (warm up and stabilization time).
9. Install a clean, new air filter into the HVAC system.
10. Depress the ZERO/CLEAN button ONCE. The STATUS LED will
9. Install a clean, new air filter into the HVAC system.
10. Depress the ZERO/CLEAN button ONCE. The STATUS LED will
blink yellow for several seconds while the
FILTERSCAN
®
records
the system
’s FAN OFF condition, then turn to blinking green. This
indicates proper operation and that you are ready to move to next
step. If the unit detects the zero air flow is out of limits, the STATUS
LED will blink red. In this case, check to see that the HVAC system
blower fan is OFF and no conditions exist during this part of the
calibration that would cause air to be moving within the HVAC ducts,
such as opening and closing of doors or windows. If no such
condition exists, contact the company that you purchased the
step. If the unit detects the zero air flow is out of limits, the STATUS
LED will blink red. In this case, check to see that the HVAC system
blower fan is OFF and no conditions exist during this part of the
calibration that would cause air to be moving within the HVAC ducts,
such as opening and closing of doors or windows. If no such
condition exists, contact the company that you purchased the
FILTERSCAN
®
from for repair information.
11. Adjust the thermostat temperature adjustment to either increase or
decrease the room temperature by at least four degrees, enough to
signal the HVAC system to turn on heating or cooling.
signal the HVAC system to turn on heating or cooling.
12. Once the HVAC system blower fan turns on, wait one minute for the
blower fan to stabilize.
13. Depress the ZERO/CLEAN button once. The STATUS LED should
turn from blinking green to blinking yellow for several minutes. This
indicates that the unit is calibrating itself to the air filter and HVAC
system into which it is installed. Once calibration is completed, the
STATUS LED will blink green a few times then turn off.
indicates that the unit is calibrating itself to the air filter and HVAC
system into which it is installed. Once calibration is completed, the
STATUS LED will blink green a few times then turn off.
14. Return the thermostat to normal operating temperature. This
concludes the installation of the
FILTERSCAN
®
Monitor.
15. The SERVICE FILTER control is a fine tuning adjustment that has
been calibrated to the mid-range, Recommended Setting at the
factory. This control allows the user to change the point at which the
clog alarm will be triggered. Turning the SERVICE FILTER adjustment
clockwise will cause the FILTERSCAN
factory. This control allows the user to change the point at which the
clog alarm will be triggered. Turning the SERVICE FILTER adjustment
clockwise will cause the FILTERSCAN
®
to issue an alarm at a lower
level of filter clogging. Turning the SERVICE FILTER adjustment
counter-clockwise will cause the FILTERSCAN
counter-clockwise will cause the FILTERSCAN
®
to issue an alarm at a
higher level of filter clogging.
R
eceiver
I
nstallation – Wireless Option Only
1. Remove the front cover of the Receiver by depressing the latch at the
top of the Receiver housing, rotating the front cover downward, and
lifting the front cover out of the housing.
lifting the front cover out of the housing.
Formatted: Indent: Left: 1.97", Outline
numbered + Level: 2 + Numbering Style: 1, 2,
3, … + Start at: 1 + Alignment: Left + Aligned
at: 2.08" + Tab after: 2.33" + Indent at:
2.33"
Formatted: Indent: Left: 1.97", Numbered +
Level: 1 + Numbering Style: 1, 2, 3, … + Start
at: 1 + Alignment: Left + Aligned at: 0.03" +
Tab after: 0.28" + Indent at: 0.28", Tab stops:
Not at 0.28"