UTC Fire & Security Americas Corporation Inc 787E-SIMON Manual De Usuario

Descargar
Página de 44
1
About This Manual
About This Manual
This manual provides information for planning, installing, pro-
gramming, and testing this security system. When necessary, 
this manual refers you to other documentation included with 
compatible devices.
Planning sheets are included for you to record sensor locations 
and software programming settings.
Special Installation Requirements
This security system can be used as a fire warning system, an 
intrusion alarm system, an emergency notification system, or 
any combination of the three.
Some installations may require configurations dictated by city/
state codes, insurance, or Underwriter’s Laboratories (UL). 
This section describes the various component and configura-
tion listings.
UL Listed Installations
This section describes the requirements for UL Listed installa-
tions.
Basic System
Control Panel (60-875-95R or 60-875-01-95R)
Backup Battery 6V 1.2 AH (34-025)
Standard Class II 9 VAC, 700 mA Power Transformer 
(22-109-ITI) or Class II 9 VAC, 700 mA Line Carrier 
Power Transformer (22-129-ITI)
Hardwire Interior Siren (13-374) or Hardwire Exterior 
Siren (13-046)
Household Burglary Alarm System Unit (UL 1023)
Basic system, plus:
Hardwire Magnetic Contact (13-068 or 13-071) or 
Wireless Learn Mode Door/Window Sensor (60-362)
Option 01: Panel Piezo Beeps set to on
Option 10: Entry Delay set to 45 seconds or less
Option 11: Exit Delay set to 60 seconds or less
Option 19: RF Timeout set to 24 hours
Option 29: Control Panel Alarms turned on
Option 38: Auto Arm set to off
Option 39: Siren Timeout set to 4 minutes or more
Option 40: Trouble Beeps set to on
Option 50: RF Jam Detect set to on
Option 53: Hardwire Siren Supervision set to on if
Option 29: Control Panel Alarms is set to off
Option 59: Exit Extension set to off
Option 67: Quick Exit set to off
Household Fire Warning System (UL 985)
Basic system, plus:
Wireless Smoke Sensor 60-506-319.5 or 60-838-95 
learned into sensor group 26
Option 01: Panel Piezo Beeps turned on
Option 19: RF Timeout set to 4 hours
Option 24: AC Power Failure Report set to on
Option 26: Fail to Communicate set to on
Option 29: Control Panel Alarms set to on
Option 39: Siren Timeout set to 4 minutes or more
Option 40: Trouble Beeps set to on
Option 50: RF Jam Detect set to on
Option 53: Hardwire Siren Supervision set to on if
Option 29: Control Panel Alarms is set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all con-
nected devices is limited to 25 mA (during normal standby 
conditions) using a 1.2 AH battery.
UL 1635 Digital Alarm Communicator System
Same as UL 1023 & 985, plus:
Note 
These option settings are in addition to UL 1023 and 985 
and are required only if the system is set up for Central 
station reporting.
Option 12: Phone Mod 1 set to 0 or 1
Option 16: Auto Phone Test set to 001
Option 19: RF Timeout set to 4 hours
Option 24: AC Power Failure Report set to on
Option 25: CPU Low Battery Report set to on
Option 50: RF Jam Detect set to on
Central Station Reporting
The panel has been tested with the following central station 
receivers using SIA and Contact ID reporting formats:
Radionics D6600 Central Station Receiver
Sur-Gard Central Station Receiver with models 
SG-DRL2A and SG-CPM2
UL Canada Listed Installations
This section describes the requirements for CUL (UL Canada) 
Listed installations.
Canadian Standards CSA Certified Accessories
Residential Burglary Alarm System Unit
(ORD-C1023-1974)
Basic system as described for “UL Listed Installations” plus:
Hardwire Magnetic Contact (13-068 or 13-071) or Wire-
less Learn Mode Door/Window Sensor (60-362)
Option 39: Siren Timeout set to 5 minutes or more
Residential Fire Warning System Control Unit 
(ULC-S545-M89)
Basic system as described for “UL Listed Installations” plus:
Wireless Smoke Sensor 60-506-319.5 or 60-838-95 
learned into sensor group 26
Option 01: Panel Piezo Beeps turned on
Option 19: RF Timeout set to 4 hours
Option 40: Trouble Beeps set to on
Option 39: Siren Timeout set to 5 minutes or more
For 24-hour backup, the total current draw for all con-
nected devices is limited to 33 mA (during normal standby 
conditions) using a 1.2 AH battery.