Benning IT 120 B 044102 Manual De Usuario
Los códigos de productos
044102
40
Displayed results:
Z
Z
Loop impedance
I
SC
Prospective short-circuit current
Lim
Low limit of prospective short-circuit current value
Save displayed results for documentation purposes. Refer to chapter 6.1 for further information on
setting functions and saving of measurement results (BENNING IT 120 B only).
setting functions and saving of measurement results (BENNING IT 120 B only).
Note:
- Measurement of the loop impedance (Zs
- Measurement of the loop impedance (Zs
rcd
) does not normally trip an RCD. However, the trip
limit may be exceeded as a result of leakage current flowing to the PE protective conductor or
via a capacitive connection between L and PE conductors.
via a capacitive connection between L and PE conductors.
- The specified accuracy of tested parameters is valid only if the mains voltage is stable during
the measurement.
5.5 Line impedance and prospective short-circuit current (Zl/ Ik)
Line impedance is a complex AC impedance within the current loop when a short-circuit to the
neutral conductor occurs (conductive connection between phase conductor and neutral conductor
in single-phase system or between two phase conductors in three-phase system). A 2.5 A test cur-
rent is used to perform line impedance measurement.
Prospective short-circuit current is calculated as follows:
neutral conductor occurs (conductive connection between phase conductor and neutral conductor
in single-phase system or between two phase conductors in three-phase system). A 2.5 A test cur-
rent is used to perform line impedance measurement.
Prospective short-circuit current is calculated as follows:
L
n
PFC
R
scaling factor
U
I
-
x
=
N(L)
where
U
n
Voltage range
115 V
100 V
≤ U
L-PE
< 160 V
230 V
160 V
≤ U
L-PE
≤ 264 V
400 V
264 V
< U
L-PE
≤ 440 V
Because of different definitions of the prospective short-circuit current IPSC in different countries
the user can set the scaling factor in the Setup menu (See chapter 4.4.2).
the user can set the scaling factor in the Setup menu (See chapter 4.4.2).
How to perform line impedance measurement:
Step 1
Step 1
Select Zl/Ik (L-N/ L) (line impedance) with the function selector switch. The following
menu is displayed:
menu is displayed:
Fig. 5.33: Line impedance measurement menu
Connect the test cable to the BENNING IT 110/ BENNING IT 120 B.
Step 2
Set the following measuring parameters:
-
Fuse type
-
Fuse current rating
-
Fuse trip-out time