Benning IT 120 B 044102 Manual De Usuario
![Benning](https://files.manualsbrain.com/attachments/2c6ac7cf379f61138af1e1f7a2711d87127cf48a/common/fit/150/50/0e125d4eb29c2f02050a306b8bcb2f3c8bc501b32f738eedf660cc9a30a0/brand_logo.gif)
Los códigos de productos
044102
77
Contact voltage limiting value
25 V or 50 V
The contact voltage is calculated relating to I
∆N
(standard) or 2
× I
∆N
(selective).
For the contact voltage, the fault loop resistance is calculated as follows:
N
C
L
I
U
R
∆
=
Tripping time
The entire measuring range complies with the requirements specified in EN61557-6. The specified
accuracies apply to the entire operating range.
accuracies apply to the entire operating range.
Standard FI/RCD (undelayed)
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 300 (½
× I
∆N
, I
∆N
)
1
± 3 ms
0 ÷ 150 (2
× I
∆N
)
1
0 ÷ 40 (5
× I
∆N
)
1
Selective FI/RCD (delayed)
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 500 (½
× I
∆N
, I
∆N
)
1
± 3 ms
0 ÷ 200 (2
× I
∆N
)
1
0 ÷ 150 (5
× I
∆N
)
1
Testing current ½
× I
∆N
, I
∆N
, 2
× I
∆N
, 5
× I
∆N
5
× I
∆N
does not apply to I
∆N
≥ 100 mA (FI/RCD of types AC, A)
2
× I
∆N
does not apply to I
∆N
≥ 500 mA (FI/RCD of type AC) or I
∆N
≥ 300 mA (FI/RCD of type A)
1
× I
∆N
does not apply to I
∆N
≥ 1000 mA (FI/RCD of type AC) or I
∆N
≥ 500 mA (FI/RCD of type A)
Tripping current
Tripping current (I
∆N
= 10 mA)
The measuring range complies with the requirements specified in EN61557-6. The specified accu-
racies apply to the entire operating range.
racies apply to the entire operating range.
Measuring range I
∆
Resolution I
∆
Accuracy
0.2
× I
∆N
÷ 1.1
× I
∆N
(AC type)
0.05
× I
∆N
± 0.1
× I
∆N
0.2
× I
∆N
÷ 2.2
× I
∆N
(A type)
0.05
× I
∆N
± 0.1
× I
∆N
Tripping current (I
∆N
≥ 30 mA)
Der Messbereich entspricht den Anforderungen von EN61557-6. Die angegebenen Genauigkeiten
gelten für den gesamten Betriebsbereich.
Measuring range I
∆
Resolution I
∆
Accuracy
0.2
× I
∆N
÷ 1.1
× I
∆N
(AC type)
0.05
× I
∆N
± 0.1
× I
∆N
0.2
× I
∆N
÷ 1.5
× I
∆N
(A type, I
∆N
≥ 30 mA)
0.05
× I
∆N
± 0.1
× I
∆N
Tripping time
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 300
1
± 3 ms