Contact voltage limiting value   
 
25 V or 50 V
The contact voltage is calculated relating to I
∆N
 (standard) or 2 
× I
∆N
 (selective).
For the contact voltage, the fault loop resistance is calculated as follows:
N
C
L
I
U
R
=
Tripping time
The entire measuring range complies with the requirements specified in EN61557-6. The specified
accuracies apply to the entire operating range.
Standard FI/RCD (undelayed)
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 300 (½ 
× I
∆N
, I
∆N
)
1
± 3 ms
0 ÷ 150 (2 
× I
∆N
)
1
0 ÷ 40 (5 
× I
∆N
)
1
Selective FI/RCD (delayed)
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 500 (½ 
× I
∆N
, I
∆N
)
1
± 3 ms
0 ÷ 200 (2 
× I
∆N
)
1
0 ÷ 150 (5 
× I
∆N
)
1
Testing current  ½ 
× I
∆N
, I
∆N
, 2 
× I
∆N
, 5 
× I
∆N
× I
∆N
 does not apply to I
∆N
≥ 100 mA (FI/RCD of types AC, A)
× I
∆N
 does not apply to I
∆N
≥ 500 mA (FI/RCD of type AC) or I
∆N
≥ 300 mA (FI/RCD of type A)
× I
∆N
 does not apply to I
∆N
≥ 1000 mA (FI/RCD of type AC) or I
∆N
≥ 500 mA (FI/RCD of type A)
Tripping current
Tripping current (I
∆N
 = 10 mA)
The measuring range complies with the requirements specified in EN61557-6. The specified accu-
racies apply to the entire operating range.
Measuring range I
Resolution I
Accuracy
0.2 
× I
∆N
 ÷ 1.1 
× I
∆N
 (AC type)
0.05 
× I
∆N
 
± 0.1 
× I
∆N
 
0.2 
× I
∆N
 ÷ 2.2 
× I
∆N
 (A type)
0.05 
× I
∆N
 
± 0.1 
× I
∆N
 
Tripping current (I
∆N
≥ 30 mA)
Der Messbereich entspricht den Anforderungen von EN61557-6. Die angegebenen Genauigkeiten 
gelten für den gesamten Betriebsbereich.
Measuring range I
Resolution I
Accuracy
0.2 
× I
∆N
 ÷ 1.1 
× I
∆N
 (AC type)
0.05 
× I
∆N
 
± 0.1 
× I
∆N
 
0.2 
× I
∆N
 ÷ 1.5 
× I
∆N
 (A type, I
∆N
≥ 30 mA)
0.05 
× I
∆N
 
± 0.1 
× I
∆N
Tripping time
Measuring range (ms)
Resolution (ms)
Accuracy
0 ÷ 300