Benning IT 120 B 044102 Manual De Usuario

Los códigos de productos
044102
Descargar
Página de 80
79
Nominal input voltage    
 
 
55 V / 63 V (45 Hz ÷ 65 Hz)
Test options  
 
 
 
 
L1-PE and L2-PE
No tripping of the FI/RCD
12.4.3 Line resistance and prospective short-circuit current
Line resistance
In compliance with EN61557-3, the measuring range is between 0.25 Ω ÷ 1999 Ω.
Measuring range (Ω)
Resolution (Ω)
Accuracy
0.00 ÷ 19.99
0.01
±(5 % of reading + 5 digits)
20.0 ÷ 99.9
0.1
100 ÷ 1999
1
*) The accuracy can be affected by strong noise of the mains voltage.
Prospective short-circuit current (calculated value)
Measuring range (A)
Resolution (A)
Accuracy
0.00 ÷ 19.99
0.01
Please observe the accu-
racy of the line resistance 
measurement.
20.0 ÷ 99.9
0.1
100 ÷ 999
1
1.00k ÷ 9.99k
10
10.0 ÷ 24.4k
100
Calculation of I
PFC 
 
 
  
I
PFC 
= U
N
 
× k
SC
 / Z
L-N
 
 
 
 
 
 
 
U
N
= 110 V, (90 V ≤ U < 121 V)
Testing current   
 
 
 
3.1 A (10 ms)
Nominal input voltage   
 
 
110 V (45 Hz ÷ 65 Hz