List of Combustion Test Data
Display Name
Description of Measurement or Calculation
O
2
% Oxygen
CO
Carbon Monoxide (1)
EFF
Combustion Efficiency
CO
2
% Carbon Dioxide
T-STK
Stack Temperature
T-AIR
Primary/Ambient Air Temperature as measured either internally or by
an optional external thermocouple plugged into the analyzer’s T-AIR
connector.
an optional external thermocouple plugged into the analyzer’s T-AIR
connector.
EA
% Excess Air
CO(#)
Carbon Monoxide ppm level referenced to a % of oxygen (2)
NO
Nitric Oxide (1)
NO
2
Nitrogen Dioxide (1)
NOx
Oxides of Nitrogen (NO and NO
2
combined) (1)
SO
2
Sulfur Dioxide (1)
NO(#)
Nitric Oxide ppm level referenced to a % of oxygen (2)
NO
2
(#)
Nitrogen Dioxide ppm level referenced to a % of oxygen (2)
NOx(#)
Oxides of Nitrogen ppm level referenced to a % of oxygen (2)
SO
2
(#)
Sulfur Dioxide ppm level referenced to a % of oxygen (2)
NO-T
Nitric Oxide Sensor Temperature (3)
(1) See page 27 for pollution unit of measure selected.
(2) The “#” represents the selected oxygen reference level of between 0 and 15% (see
(2) The “#” represents the selected oxygen reference level of between 0 and 15% (see
(3) Only shown if selected in the Run/Hold Format menu (see page 37).
NOTE: Stars (* * *) appear in measurement and calculation fields of
sensors that are not installed.
sensors that are not installed.
5.6. Selecting a Pressure Label
The pressure measurement can be labeled with types including, differential
across heat exchanger, draft reading, and differential pressure. See page 47 for
pressure and draft measurement procedures. Label data as follows.
across heat exchanger, draft reading, and differential pressure. See page 47 for
pressure and draft measurement procedures. Label data as follows.
1. Display the MAIN MENU by pressing the MENU (F2) button. If
necessary, press ESC until MENU appears above F2.
2. Use the
▲▼ buttons to highlight PRESSURE, and then press ENT to
display the PRESSURE MENU.
3. Use the
◄► buttons to scroll through the available pressure label
types. The current label is used, saved, and printed with the record.