Circuit Board LED Indicators
  LED # 
LED Color 
Illuminates:
 
 
 
Green 
When the compressor should be ON.
 
  2 Cabinet 
Red 
When the cabinet temperature is above 50 degrees F.
 
 
 
 
Flashes slowly when cabinet temperature exceeds 50 degrees F for 4 
hours. Dispense functions are locked out under this condition. Power 
down the dispenser to reset.
 
 
 
Flashes rapidly if dispense is attempted in lockout condition.
 
 
 
Open cabinet thermistor circuit will flash #2 and #3 LED’s 1 time every 3 
seconds.
 
 
 
Shorted cabinet thermistor will turn  #2 and #3 LED’s on steady.
 
  3 Cabinet 
Green 
When cabinet temperature is below 50 degrees F.
 
  4 Bath 
Red 
When bath temperature is above 34 degrees F.
 
 
 
 
 
 
Flashes slowly when compressor is in a 6 minute delay period.
 
 
 
Open bath thermistor circuit will flash #4 and #5 LED’s 1 time every 3 
seconds. The compressor will not run under this condition.
 
 
 
Shorted bath thermistor circuit will flash #4 and #5 LED’s 2 times every 3 
seconds. The compressor will not run under this condition.
 
  5 Bath 
Green 
When bath temperature is below 34 degrees F.