TROUBLESHOOTING (cont.)
Check for "ON" position or no con-
tinuity - replace switch.
Clean filter and fins or replace con-
denser filter. (Filter not supplied on 
some machines).
A) Check for 120V or 230V AC. Re-
place fan motor or check fan blades 
for obstructions.
B) Check compressor LED on circuit 
board. If ON, relay coil should have 
power (120 or 230 VAC).
Check compressor relay coil for 120 
or 230vac.
NOTE:  Always  check  power  with 
coil  attached.  If  compressor  LED 
is ON and no 120 or 230vac - re-
place board. If yes, 120 or 230vac 
- replace relay.
Note: Relay contacts are normally 
open.
Check compressor thermal overload 
(N/C). If open check for dirty con-
denser filter or adequate ventilation 
and space around machine.
Check refrigeration system for leaks 
and proper charge.
(A) Set switch to ON position.
(B) Check switch and harness for 
proper continuity.
Check all previous items that pre-
tain to refrigeration or cold water 
recirculation
1. Compressor ON/OFF switch.
2. Dirty condenser filter or fins.
3. Condenser fan not running.
4.  Compressor  relay  not  activat-
ing.
5. Compressor not running.
6.  Compressor  running  and  not 
cooling.
1.  Check  Dispense  Lockout 
switch.
1. Refrigeration or cold water recir-
culation system.
Refrigeration
Dispense stations not working.
Note: Cooling failure or excessive 
bath and cabinet temperatures for 
more  than  4  hours  will  result  in 
dispense lockout or no dispense.
Dispenser Locked Out
Dispense stations not working.
Cooling system failure.
PROBLEM
PROBABLE CAUSE
REMEDY
38945 061506