User Menu Parameters
105
Liebert
®
 iCOM
®
Event Log
Event Log—The event log displays all events and actions generated by the unit. When multiple 
units are networked the event log shows results for the whole system. Each event shows the unit that 
generated the alarm, time and date stamp, a description and the event type.
The event log contains the last 400 events generated by the unit. Events include such occurrences as 
unit On/Off commands, alarms, warnings and messages. The event log has two views: system view 
and unit view. When the event log is first entered, the system view is displayed. The system view lists 
events that have occurred at the unit and other units, if configured in a U2U network. Pressing the 
Right arrow while viewing the event log for the system view allows the user to see unit-specific 
events. The unit name and number will appear in the upper right corner for the unit selected. Each 
event shows the unit that generated the alarm, time and date stamp, a description and the event 
type. As new events are stored in the log, older events are pushed further down the list.
Once the event log reaches 400 events, the oldest events are erased as new events are stored.
View Network
View Network—The view network screen provides an overview of the Liebert iCOM network and a 
status of each unit. This screen will provide the unique unit name given to the unit. If no name is 
given, then only the unit number will be displayed.