User Menu Parameters
107
Liebert
®
 iCOM
®
Figure 90 Set alarms screen, page 2
U213 Supply Sensor Alarms—Enables or disables the supply sensor alarms. When enabled, the 
supply temperature and humidity values will be compared to a high and low setting.
U214 High Supply Temperature—Sets the temperature at which the High Supply Temperature 
Alarm is activated. This parameter is adjustable from 34°F to 210°F. The factory default is 75°F.
U215 Low Supply Temperature—Sets the temperature at which the Low Supply Temperature 
Alarm is U21activated. This parameter is adjustable from 34°F to 210°F. The factory default is 50°F. 
U219 Remote Sensor Alarms—Enables or disables the Remote sensor alarms. When enabled, the 
Remote temperature values will be compared to a high and low setting.
U220 High/Low Remote Temperature—Enables or disables remote air alarm. When enabled, the 
high and low temperature alarm will allow a user to adjust the point at which the actual remote 
temperature activates a Low Remote Temperature Alarm. This parameter is used when common 
alarm points will be shared by all sensors. Otherwise, the remote sensors can be set individually on 
page 3. This parameter is adjustable from 34°F to 210°F. The factory default 50°F.
U221 Separate thresholds are on page 3—Informational