User Menu Parameters
Liebert
®
iCOM
®
106
7.3
User-Set Alarms Menu Screens
Set Alarms allow the user to view and modify basic temperature and humidity alarms and thresholds
Figure 89 Set alarms screen, page 1
U202 Return Sensor Alarms—Enables or disables the return sensor alarms. When enabled, the
return temperature and humidity values will be compared to a high and low setting.
U203 High Return Temperature—Allows a user to adjust the point at which the actual return
U203 High Return Temperature—Allows a user to adjust the point at which the actual return
temperature activates a High Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The factory default is 80°F.
U204 Low Return Temperature—Allows a user to adjust the point at which the actual return
U204 Low Return Temperature—Allows a user to adjust the point at which the actual return
temperature activates a Low Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The factory default is 65°F.
U205 High Return Humidity—Allows a user to adjust the point at which the actual return
U205 High Return Humidity—Allows a user to adjust the point at which the actual return
humidity activates a High Humidity Alarm. This parameter is adjustable from 1% to 99%. The factory
default is 60%F.
U206 Low Return Humidity—Allows a user to adjust the point at which the actual return
U206 Low Return Humidity—Allows a user to adjust the point at which the actual return
humidity activates a Low Humidity Alarm. This parameter is adjustable from 1% to 99%. The factory
default is 40%F.
U207 Sensor A Alarms—Enables or disables the alarms for reference Sensor A. When enabled, the
U207 Sensor A Alarms—Enables or disables the alarms for reference Sensor A. When enabled, the
Sensor A temperature and humidity values will be compared to a high and low setting.
U208 High Temperature Sensor A—Allows a user to adjust the point at which the actual Sensor A
U208 High Temperature Sensor A—Allows a user to adjust the point at which the actual Sensor A
temperature activates a High Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The factory default is 80°F.
U209 Low Temperature Sensor A—Allows a user to adjust the point at which the actual Sensor A
U209 Low Temperature Sensor A—Allows a user to adjust the point at which the actual Sensor A
temperature activates a Low Temperature Alarm. This parameter is adjustable from 34°F to 210°F.
The factory default is 65°F.
U210 High Humidity Sensor A—Allows a user to adjust the point at which the actual Sensor A
U210 High Humidity Sensor A—Allows a user to adjust the point at which the actual Sensor A
humidity activates a High Humidity Alarm. This parameter is adjustable from 1% to 99%. The factory
default is 60%F.
U211 Low Humidity Sensor A—Allows a user to adjust the point at which the actual Sensor A
U211 Low Humidity Sensor A—Allows a user to adjust the point at which the actual Sensor A
humidity activates a Low Humidity Alarm. This parameter is adjustable from 1% to 99%. The factory
default is 40%F.