User Menu Parameters
109
Liebert
®
iCOM
®
U240 SP Transducer High Range—Sets the pressure range at which the High Static Pressure Out
of Range Alarm is activated. This parameter range is adjustable from 0.000 - 1.405 inWC. The factory
default is 1.284 inWC.
U241 SP Transducer Low Range—Sets the pressure range at which the Low Static Pressure Out
U241 SP Transducer Low Range—Sets the pressure range at which the Low Static Pressure Out
of Range Alarm is activated. This parameter range is adjustable from 0.000 - 1.395 inWC. The factory
default is 0.000 inWC.
7.4
User-Sensor Data Menu Screens
Sensor Data shows the readings and status of standard and optional sensors.
Figure 93 Sensor data screen, page 1
U301 Sensor A: T / H—Shows the calibrated Sensor A temperature (left hand value) and humidity
(right hand value) if the optional reference sensor is connected to the Liebert iCOM controller area
network (CAN) bus. A reference sensor can be connected to any type of Liebert iCOM unit. Sensor A is
selected by setting the DIP switches on the temperature and humidity board. Refer to 4.3.2 - DIP
Switch Settings.
U302 Sensor B: T1 / T2 / H—Shows the calibrated Sensor B temperature (left hand value), second
U302 Sensor B: T1 / T2 / H—Shows the calibrated Sensor B temperature (left hand value), second
temperature reading in the if sensor B is a 2T, and humidity (right hand value) if sensor B is a T/H
sensor. Sensor B is an optional reference sensor connected to the Liebert iCOM controller area
network (CAN) bus. A reference sensor can be connected to any type of Liebert iCOM unit. Sensor B is
selected by setting the DIP switches on the temperature and humidity board. Refer to 4.3.2 - DIP
Switch Settings.
U303 Sensor C: T1 / T2 / H—Shows the calibrated Sensor C temperature (left hand value), a second
U303 Sensor C: T1 / T2 / H—Shows the calibrated Sensor C temperature (left hand value), a second
temperature reading if sensor C is a 2T (middle), and humidity (right hand value) if sensor C is a T/H
sensor. Sensor C is an optional reference sensor connected to the Liebert iCOM controller area
network (CAN) bus. Sensor C is selected by setting the DIP switches on the temperature and
humidity board. Refer to 4.3.2 - DIP Switch Settings. A reference sensor 'C' can be connected to any
type of Liebert iCOM unit unless the unit is equipped with an air side economizer. When the unit has
an air side economizer, this parameter represents the outside air temperature and humidity. See the
description below for more details.
U303 Outdoor Temp / Hum—Reads the calibrated outdoor temperature (left hand value) and
U303 Outdoor Temp / Hum—Reads the calibrated outdoor temperature (left hand value) and
humidity (right hand value) for air side economizer units. These readings are used to determine air
side economizer eligibility. It is determined by comparing the temp between the room and outdoor air
temperature.
U304 FC Fluid Temperature—Displays the calibrated temperature of the incoming water on units
U304 FC Fluid Temperature—Displays the calibrated temperature of the incoming water on units
equipped with a free-cooling coil.