User Menu Parameters
Liebert
®
 iCOM
®
108
Figure 91 Set alarms screen, page 3
U224-U233 High/Low Remote 01 - 10— Sets the High and Low remote temperature sensor alarm 
points individually for each sensor when the parameter separate thresholds is set to disabled. The 
range for both parameters is 34°F to 210°F. The default setting for low alarm is 55°F. The default 
setting for high alarm is 90°F.
Figure 92 Set alarms screen, page 4
U235 Static Pressure Messages—Enables or disables the static pressure alarms. 
U236 High Static Pressure—Sets the pressure at which the High Static Pressure Alarm is 
activated. This parameter is adjustable from 0.000 - 1.405 inWC. The factory default is 1.284 inWC.
U237 Low Static Pressure—Sets the pressure at which the Low Static Pressure Alarm. This 
parameter is adjustable from 0.000 - 1.395 inWC. The factory default is 0.000 inWC.
U238 SP Messages During Unit Off—Enables or disables the static pressure alarms when the unit 
is OFF.
U239 SP Messages on Fan Adjust—Enables or disables the static pressure alarms when the fan 
has been adjusted due to special events. These events include an adjustment for heating, 
humidification, dehumidification, motor overload / EC fan fault or loss of airflow.