Service Menu Parameters
Liebert
®
 iCOM
®
156
Figure 147
iCOM-DO events setup screen, page 2 of 3
S733-740, S744-S751—The lines are divided into four columns.
• Event Description—Read-only parameter that describes the event type that may activate an 
output on the Liebert iCOM-DO
. Each event description may reflect a status or alarm, 
depending on the line. 
• ID—Displays the number of the Liebert iCOM-DO. Currently only one Liebert iCOM-DO card is 
supported. The ID must match the S721 to function.
• Output #—Shows which output is tied to a particular alarm. The default values are set to be the 
same output as the Liebert ENV-DO
 card, the predecessor to the Liebert iCOM-DO. The ID’s are 
linked to S725.
• Status—Read-only value that shows the state of the output.
Figure 148
Liebert iCOM-DO events setup screen, page 3 of 3