Service Menu Parameters
157
Liebert
®
 iCOM
®
8.7
Service-Sensor Calibration Menu Screens
Sensor Calibration allows the user to view readings of connected sensors and calibrate values as 
needed.
Figure 149
Sensor calibration setup screen, page 1 of 12
S602 Return Temperature—Adjusts the return temperature reading from the actual sensor to 
compensate for any error of the sensor or to match other sensors in the room.
S603 Calibrated Return Temperature—Shows the adjusted temperature value of the return 
sensor. This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
S604 Return Humidity—Adjusts the return humidity reading from the actual sensor to compensate 
for any error of the sensor or to match other sensors in the room.
S605 Calibrated Return Humidity—Shows the adjusted humidity value of the return sensor. This 
value is the actual sensor reading (+ or -) the offset “Return Humidity”.
S606 DigiScroll 1 NTC—Adjusts the digital scroll 1 NTC reading from the actual sensor to 
compensate for any error or drift of the sensor.
S607 Calibrated Digiscroll 1 NTC—Shows the adjusted Digital Scroll 1 NTC sensor value. This 
value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
S608 Digiscroll 2 NTC—Adjusts the digital scroll 1 NTC reading from the actual sensor to 
compensate for any error or drift of the sensor.
S609 Calibrated Digiscroll 2 NTC—Shows the adjusted Digital Scroll 1 NTC sensor value. This 
value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC.”
S610 Outdoor Sensor—Adjusts the outdoor temperature reading from the actual sensor to 
compensate for any error of the sensor or to match other sensors in the room.
S611 Calibrated Outdoor Sensor—Shows the adjusted temperature value of the outdoor sensor. 
This value is the actual sensor reading (+ or -) the offset “Outdoor Sensor.”