Service Menu Parameters
163
Liebert
®
 iCOM
®
Figure 157
Sensor calibration/setup screen, page 10 of 12
S6B1 Chilled Water Sensor Type—Used for selecting the type and number of fluid sensors 
installed. Two options are available: 2T and Dual 2T. The 2T option is used on units equipped with 
one flow meter and Dual 2T is used for units with two flow meters.
S6B2 CW Temp Sensor Placement (CW T Sensor C1 / C2 Placement w/Dual 2T)—Allows 
swapping the chilled water sensor readout in the display. In the event the 2T sensor probe is installed 
backward, this allows the user to correct the readout in the software. On dual-sensor applications, a 
parameter will be available for each sensor. Two options are available: Norm and Rev. The factory 
default is Norm.
S6B3 CW Circuit 1 Offset Sns In/Out—Adjusts the fluid temperature value of the fluid 
temperature inlet and outlet probes. This value is the actual sensor reading (+ or -) the offset “CW 
Circuit 1 Calibrated In/Out.”
S6B4 CW Circuit 1 Calibrated In/Out—Shows the adjusted fluid temperature value of the fluid 
temperature inlet and outlet probes. This value is the actual sensor reading (+ or -) the offset “CW 
Circuit 1 Calibrated In/Out.”
S6B5 CW Circuit 2 Offset Sns In/Out—Adjusts the fluid temperature value of the fluid 
temperature inlet and outlet probes. This value is the actual sensor reading (+ or -) the offset “CW 
Circuit 2 Calibrated In/Out.”
S6B6 CW Circuit 2 Calibrated In/Out—Shows the adjusted fluid temperature value of the fluid 
temperature inlet and outlet probes. This value is the actual sensor reading (+ or -) the offset “CW 
Circuit 2 Calibrated In/Out.”
S6B7 Cooling Load Calc. Enabled—Allows enabling or disabling the cooling load calculation. Two 
options are available: No and Yes. If Yes is selected, a cooling load output field will populate. Cooling 
load output options include kW and kBtuh. The factory default for the cooling load calculation is No.
S6B8 Cooling Load Filter Time—Cooling load is based on an average calculation of input 
temperature and flow. This parameter sets duration of the average used for the cooling output 
reading. This parameter is adjustable from 30 to 300 sec. The factory default is 60 sec.
S6B9 Show CoolLoad on Main Screen—Allows selecting whether the cooling load calculation is 
displayed in the Unit View>Main Screen. The options are: No and Yes. The factory default is No.
S6C1 Disable CoolLoad @ Unit On for—Delays the cooling load calculation start point after a unit 
has turned On. During delay time programmed, cooling capacity will not be shown through the local 
display or through monitoring. The range is 0-10 minutes with a factory default of 5 minutes. To show 
cooling load as soon as the unit powers up, set the parameter to 0.
S6C2 Cooling Load (Cooling Load C1 + C2 w/Dual 2T & flow meters)—Displays the total 
calculated cooling load in kW or kBtu/h. C1 and C2 are added together and displayed here on 
applicable models.
S6C3 Cooling Load C2 / C1—Displays the calculated cooling load in kW or kBtu/h by circuit on 
applicable models.