Operation
Liebert
®
 iCOM
®
32
Temperature Deadband
The deadband range is used to widen the setpoint and prevents small temperature changes from 
activating compressors and valves. When the air temperature falls within the deadband, the control 
operates the same as if the temperature equaled the setpoint exactly. This setting helps maximize 
component life by preventing excessive component cycling. Figure 25 illustrates how the 
temperature proportional band and deadband is evenly divided on either side of the temperature 
setpoint.
The parameter AutoSet Enable, found in Service Menu, Setpoints, automatically sets the 
proportional bands for temperature and humidity, and both the integration time factors according to 
the type of unit (chilled water, single or dual compressor)
.
3.3.2 Compressor Control
Depending on its type, a Liebert cooling unit may have one or two compressors with or without 
unloaders or variable capacity.
Compressor Proportional Bands
One Single-Step Compressor Without Unloaders—One-Step
One single-step compressor, Cool 1, is started at 100% call for cooling from the temperature 
proportional band and stopped at 0% (see Figure 26).
Figure 26 One single-step compressor without unloaders
Two Single-Step Compressors Without Unloaders—Two-Step
First single-step compressor, Cool 1, is started at 50% calculated output from the temperature 
proportional band, and stopped at 0%. The second compressor, Cool 2, starts at 100% and stops at 
50% (see Figure 27).
One Compressor With an Unloader—Two-Step
The two-step compressor is started unloaded at 50%, Cool 1, calculated output from the temperature 
proportional band and stopped at 0%. At 100% the compressor starts fully loaded, Cool 2, and returns 
to unload operation at 50% (see Figure 27).
 NOTE
Before the proportional or integral setpoints can be changed, the Auto Set Enable must be 
changed to NO.
Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 2°F
75
½  Proportional Band
0%
Cooling
+ 100 % 
Cooling
71
72
73
74
70
½ Dead-
band
Cool 1
Off
Cool 1
On
Increasing Temperature