Figure 27 Two single-step compressors without unloaders or one compressor with an unloader (two-step)
Two Compressors With Unloaders—Four-Step
The first two-step compressor is started unloaded at 33% calculated output from the temperature 
proportional band and stopped at 17%. At 80%, Compressor 1 will be loaded, at 70% unloaded. 
The second compressor starts unloaded at 63% and stops at 47%. At 100%, Compressor 2 will be 
loaded, at 90% unloaded (see Figure 28).
The four stages of cooling are accomplished in the following manner:
• 1 stage: One compressor, unloaded - Cool 1
• 2 stages: Both compressors, unloaded - Cool 2
• 3 stages: One compressor, loaded and one compressor, unloaded - Cool 3
• 4 stages: Both compressors, loaded - Cool 4
Figure 28 Two compressors with unloaders (four-step)
Temp Setpoint : 70°F
Proportional Band: 8°F
Deadband : 2°F
75
1/2 Proportional Band
0%
Cooling
+ 100% 
Cooling
71
72
73
74
70
1/2 Dead-
band
Cool 1
On
Cool 2
On
Increasing Temperature
Cool 2
Off
Cool 1
Off
Cool 2
On
Temp Setpoint : 70°F
Proportional Band: 8°F
Deadband : 2°F
½ Dead-
band
Increasing Temperature
½ Proportional Band
75
74
73
72
71
70
0%
Cooling
+ 100 % 
Cooling
Cool 4
Off
Cool 2
Off
Cool 1
Off
Cool 4
On
Cool 3
On
Cool 1
On
Cool 3
Off