Operation
Liebert
®
 iCOM
®
36
3.4.1 Differential Temperatures / Controls (Comparator Circuit)
Delta T (Temperature Difference) Between Room and Fluid
The comparator circuit determines if the glycol / chilled water temperature of the second cooling 
source is low enough to provide at least partial cooling capacity. Free-Cooling Fluid Temperature is 
controlled in the User - Sensor Data menu, Figure 93. The comparator circuit has four settings 
(DT Between Room / FC Type, [Service Menu, Setpoints]):
• Disabled
• Contact
• Value
• Set
The Disabled setting is for standard compressorized and chilled water units that do not have a second 
cooling source. The Disabled setting can also be used to disable the second source of cooling.
The Contact setting is used when an external input is being used to determine when the second 
cooling source is to be activated. The external control communicates to the Liebert unit via contact 
closure.
• Closed = activate second cooling source control
• Open = deactivate second cooling source control
The Temp setting is the factory default (12°F [-11.1°C]) on free-cooling and dual cooling units. If the 
temperature difference between the second source cooling fluid parameter, Free-cooling Fluid 
Temperature (User Menu, Sensor Data) and room air is equal to or greater than the adjustable DT 
Between Room / FC Fluid (Service Menu, Setpoints) value, then the second source cooling fluid will be 
used to provide at least partial cooling.
The Set option allows free-cooling whenever the fluid temperature sensed (User Menu > Sensor Data) 
is colder than the temperature setpoint. The difference required between the temperature setpoint 
and the fluid temperature is adjusted on the following line DT2 Room / FC Fluid value (Service Menu, 
Setpoints). The second source cooling fluid will be used to provide cooling if the temperature 
difference between the second source cooling fluid parameter, Free-cooling Fluid Temperature and 
room air is equal to or greater than the adjustable DT Between Room / FC Fluid value.
Sensors used for this delta T are: room/local sensor or the return air sensor; and the glycol sensor.
If this delta T is true, the Free-cooling Status indication will show “On” instead of “Off”. The status is 
found in the User- Sensor Data menuFigure 93. The primary and secondary source of cooling will 
stage accordingly. See the next sections for more information. 
Figure 32 Second cooling source and two-step compressorized cooling
75
71
72
73
74
70
Increasing Temperature
Cool 2
On
Cool 1
On
+ 100% 
Cooling
Valve 100% 
Open
Valve 
Closed
½ Dead-
band
76
77
78
79
+ 200% 
Cooling
0%
Cooling
2nd
Source
Comp
½ Proportional Band
½ Proportional Band
Band 1: 2
nd
Source
Band 2: Compressors
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F