Emerson Liebert iCOM Manual De Usuario
Operation
35
Liebert
®
iCOM
®
3.3.3 Chilled Water Control
A variety of chilled water valves and actuators are offered depending on application requirements.
Floating point and analog actuators are common to most applications.
Floating point actuators are driven through two digital outputs: Open and Close. As default, Liebert
Floating point actuators are driven through two digital outputs: Open and Close. As default, Liebert
iCOM determines the valve position by timing how long the open or closed signals have been active
based on the valve travel time set in the Service menu / Setup submenu. The valve response may be
improved by implementing a valve feedback signal. See 3.2 - General Chilled Water Operation for
more information.
Analog driven actuators commonly work off a direct or indirect 0-10 or 2-10 VDC signal. Liebert
Analog driven actuators commonly work off a direct or indirect 0-10 or 2-10 VDC signal. Liebert
CW181 models and larger units may contain two analog valves; as default, both valves will be
controlled in parallel for cooling. Other valve staging options are available. See 3.2.3 - Custom Dual
Chilled Water Valve Staging for more information.
In all applications, the valves open and close according to a call for cooling as shown in Figure 31.
In all applications, the valves open and close according to a call for cooling as shown in Figure 31.
The chilled water control valve is adjusted proportionally as the temperature control varies the
requirement for cooling from 0% to 100%.
Figure 31 Chilled water valve control (example: cooling)
3.4
Liebert Fluid Economizer
Two types of fluid economizers are offered, GLYCOOL and Dual-Cool. GLYCOOL models are two-pipe
systems. This means that two pipes enter the unit and feed the chilled water/free-cooling coil as well
as the compressor(s) and heat exchanger (eg., Liebert Paradenser
™
, tube-in-tube condenser or brazed
plate heat exchanger). Dual-Cool units can be either two-pipe or four-pipe systems. A two-pipe unit
has two fluid lines dedicated to the secondary cooling source, and the compressor(s) heat rejection is
an air-cooled condenser. Four-pipe Dual-Cool models have two fluid pipes dedicated to chilled
water/free-cooling and two pipes for the compressor(s) heat exchanger. Each model offers a primary
DX source and a secondary chilled water or free-cooling coil.
+ 100%
Cooling
Cooling
½ Proportional Band
0% - Closed
Requested Position
100% Fully Open
0%
Setpoint
+ Temp