Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Operation
37
Liebert
®
 iCOM
®
Minimum Chilled Water Temperature—This feature allows the user to select a minimum chilled 
water temperature to prevent simultaneous operation of the chilled water (free-cooling) and 
compressor(s) on units factory-programmed to operate both sources simultaneously. This feature is 
enabled in Service>Setpoints, parameter Minimum CW Temp.
If the fluid temperature sensed is below the Minimum CW Temp Value, (Service Menu, Setpoints), 
and the Delta T (Temperature Difference) Between Room and Glycol (see 3.4.1 - Differential 
Temperatures / Controls (Comparator Circuit) is satisfied, the control will operate ONLY the 
chilled water for cooling. The compressor(s) is locked out. If cooling does not operate, (i.e., loss of 
chilled water flow), the control will override this setting and activate a compressor(s). When this 
happens, free-cooling will be locked out for one hour.
If the fluid temperature is above the minimum CW value, the control will operate the chilled water 
(free-cooling) and compressor(s) simultaneously if needed. If the Minimum CW Temp is disabled, the 
control may operate both sources as load requires.
GLYCOOL
 Cooling—Free-Cooling
GLYCOOL units may be programmed to stage cooling components in either of two ways:
• Operate free-cooling or compressor(s) to maintain temperature (factory default)
• Operate free-cooling and compressor(s) simultaneously
Caution must be taken when operating free-cooling and the compressor simultaneously on GLYCOOL 
units. Adequate flow must be provided to the unit to prevent high pressure when 100% free-cooling is 
required in addition to DX cooling. Running too cold of fluid temperature and compressor(s) 
simultaneously may cause refrigerant pressure to drop. Contact technical support at 800-543-2778 for 
more information on simultaneous operation setup.
When the unit is configured to operate free-cooling or compressors(s), free-cooling eligibility is based 
on the comparator circuit discussed in 3.4.1 - Differential Temperatures / Controls (Comparator 
Circuit). If the circuit determines free-cooling will condition the space, the valve will open and close 
as temperature deviates from the setpoint. If the comparator circuit determines that free-cooling is 
not capable of conditioning the space, control is automatically replaced by compressor(s).
During either free-cooling or compressor operation, the control uses the temperature proportional 
band to determine which operation to perform (cooling/heating) and how much capacity to provide. 
The Temperature Proportional Band is a user-defined range that is divided into two equal parts for 
cooling and heating. The Temperature Setpoint is between these two equal parts. An optional 
temperature and heating deadband range can be defined, which is equally divided on either side of 
the setpoint and separates the two halves of the proportional band.
When the unit is configured to operate free-cooling and compressor(s) simultaneously, the comparator 
circuit determines free-cooling eligibility. Free-cooling and compressor(s) are staged based on 
temperature deviation from setpoint. The cooling proportional band is divided into two parts for 
simultaneous operation, the first portion is used for free-cooling and the second for DX operation. 
Figure 32 illustrates how the cooling proportional band is broken out on a free-cooling unit with two 
step compressors.
Cooling Control Band for Simultaneous Operation = (Temperature Proportional Band/2) / 2 + 
(Temperature Deadband/2)
If the comparator circuit determines that free-cooling is ineligible for use, the compressor band will 
shift to the left.