3.6.2 SCR Reheat
SCR reheat is a type of electric reheat that provides tighter temperature control than staged electric 
reheat. SCR reheat capacity modulation is achieved by pulsing the reheat On and Off. Full capacity is 
achieved by constantly energizing the reheat. Units equipped with SCR reheat can operate in Tight or 
Standard mode. By default, cooling units with SCR reheat are factory-set to operate in Tight mode. 
The mode of operation can be set by adjusting the SCR Control Type parameter (Service Menu, 
Setpoints).
Tight Mode
In Tight mode, the compressors and reheats are operated at the same time to provide maximum 
temperature control. The temperature deadband is set to zero at the factory. In a cooling unit with 
SCR reheat and two single-step compressors, the first single-step compressor is started and full 
reheat capacity is provided at 0% calculated output from the Temperature Proportional Band. As the 
call for cooling increases from 0% to 100%, the reheat capacity is slowly reduced by pulsing the 
reheat. At 100% call for cooling, the reheat is deactivated and the second single-step compressor is 
started. As the call for cooling is reduced, the reheat capacity is slowly increased. When the call for 
cooling returns to 0%, the second single-step compressor is deactivated.
If the Temperature Proportional Band calculates a call for heating from 0% to -200%, the first 
single-step compressor remains activated and full reheat capacity is provided. Based on the factory 
defaults, the first single-step compressor is deactivated when the control reaches -200% call for 
heating. The compressor remains deactivated until the control calls for 0% heating. The compressor 
activation and deactivation points can be adjusted in the Service menu under Setpoints. Figure 43 
illustrates how a cooling unit with two single-step compressors and SCR reheat operates when the 
SCR Control Type is set to Tight mode.
Figure 43 Two single-step compressors with SCR reheat set to Tight mode
NOTE
Tight Mode is not available on chilled water units, units with variable speed fans or units with 
digital scroll compressors.
NOTE
Some cooling units are not suited for a strict NO LOAD application. These cooling units 
require a minimal load in the space. Consult factory for verification.
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 0°F
Cool 1
Off
-100 %
Heating
Cool 2
On
SCR On
Cool 1 On
Cool 2
Off
SCR
Off
-200%
Heating
100%
Cooling
0%
½ Proportional Band
½ Proportional Band
½ Proportional Band
74
65
70
66
67
68
69
71
72
73
64
63
62
Cooling 2  On
Cooling 1 On
SCR Reheat On