Emerson Liebert iCOM Manual De Usuario
Operation
51
Liebert
®
iCOM
®
Standard Mode
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for
heating. SCR reheat output is adjusted proportionally as the Temperature Proportional Band varies
the requirement for heating from 0% to -100%. Compressors operate only when there is a call for
cooling as described in 3.3.2 - Compressor Control.
Figure 44 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.
Figure 44 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.
Figure 44 Two single-step compressors with SCR reheat set to Standard mode
3.7
Humidity Control
There are a variety of humidifier options depending on model unit and application requirements. In
all humidifier applications, operation is limited to 80°F (26°C) return air temperature. If the return
air temperature reaches 80°F (26°C) or higher during operation, the humidifier will be disabled. After
reaching the lockout threshold, the temperature must fall to 75°F (24°C) or below 80°F (26.7°C) for 20
minutes before the humidifier is permitted to operate.
This safety routine does not apply to externally mounted humidifiers.
Contact technical support need assistance adjusting the humidifier lockout and/or reset point or if
This safety routine does not apply to externally mounted humidifiers.
Contact technical support need assistance adjusting the humidifier lockout and/or reset point or if
there are humidification problems as a result of this routine.
The Liebert iCOM has four humidity sensor control types: Dew Point, Relative, Compensated and
The Liebert iCOM has four humidity sensor control types: Dew Point, Relative, Compensated and
Predictive. The humidity sensor adjusts how the Temperature and Humidity Control determines the
percent requirement for humidification/dehumidification. The humidity sensor control type
parameter, Humidity Control Type, is in both the User and Service menus under Setpoints.
Dew Point—The actual return temperature and humidity measured by Liebert iCOM is used
Dew Point—The actual return temperature and humidity measured by Liebert iCOM is used
internally to determine the dew point. When dew point control is selected, the user will set the
humidity setpoint in degrees dew point and will also adjust the proportional band in degrees dew
point.
Relative—The actual return air humidity sensor reading is sent to the Temperature and Humidity
Relative—The actual return air humidity sensor reading is sent to the Temperature and Humidity
Control to determine whether and how much humidification/dehumidification is required. The actual
return air humidity reading is displayed on the Status menu. Unnecessary dehumidification can
result when overcooling occurs during a dehumidification cycle. This is because a higher than normal
relative humidity (RH) reading is caused by overcooling the room. This extends the dehumidification
cycle. Later, when the dehumidification ends and the return air temperature rises to the setpoint, the
RH reading falls. The final RH reading will then be lower than desired. If significant overcooling
occurred, the RH could be low enough to activate the humidifier.
NOTE
Using SCR in Standard mode in conjunction with variable cooling capacity (e.g., chilled water
Using SCR in Standard mode in conjunction with variable cooling capacity (e.g., chilled water
valve or digital compressor) provides ultimate capacity control and energy-efficiency gains.
Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 0°F
Proportional Band : 8°F
Deadband : 0°F
Cool 2
On
Cool 1
On
Cool 2
Off
Cool 1 Off
SCR Off
SCR
On
0%
100 %
Cooling
-100%
Heating
74
71
72
73
66
67
68
69
70
½ Proportional Band
Cooling 1 On
Cooling 2 On
½ Proportional Band
SCR On