Emerson Liebert iCOM Manual De Usuario

Descargar
Página de 196
Operation
51
Liebert
®
 iCOM
®
Standard Mode
In Standard mode, the SCR reheat operates only when the Temperature Proportional Band calls for 
heating. SCR reheat output is adjusted proportionally as the Temperature Proportional Band varies 
the requirement for heating from 0% to -100%. Compressors operate only when there is a call for 
cooling as described in 3.3.2 - Compressor Control.
Figure 44 illustrates how SCR reheat operates when SCR Control Type is set to Standard mode.
Figure 44 Two single-step compressors with SCR reheat set to Standard mode
3.7
Humidity Control
There are a variety of humidifier options depending on model unit and application requirements. In 
all humidifier applications, operation is limited to 80°F (26°C) return air temperature. If the return 
air temperature reaches 80°F (26°C) or higher during operation, the humidifier will be disabled. After 
reaching the lockout threshold, the temperature must fall to 75°F (24°C) or below 80°F (26.7°C) for 20 
minutes before the humidifier is permitted to operate.
This safety routine does not apply to externally mounted humidifiers.
Contact technical support need assistance adjusting the humidifier lockout and/or reset point or if 
there are humidification problems as a result of this routine.
The Liebert iCOM has four humidity sensor control types: Dew Point, Relative, Compensated and 
Predictive. The humidity sensor adjusts how the Temperature and Humidity Control determines the 
percent requirement for humidification/dehumidification. The humidity sensor control type 
parameter, Humidity Control Type, is in both the User and Service menus under Setpoints.
Dew Point—The actual return temperature and humidity measured by Liebert iCOM is used 
internally to determine the dew point. When dew point control is selected, the user will set the 
humidity setpoint in degrees dew point and will also adjust the proportional band in degrees dew 
point.
Relative—The actual return air humidity sensor reading is sent to the Temperature and Humidity 
Control to determine whether and how much humidification/dehumidification is required. The actual 
return air humidity reading is displayed on the Status menu. Unnecessary dehumidification can 
result when overcooling occurs during a dehumidification cycle. This is because a higher than normal 
relative humidity (RH) reading is caused by overcooling the room. This extends the dehumidification 
cycle. Later, when the dehumidification ends and the return air temperature rises to the setpoint, the 
RH reading falls. The final RH reading will then be lower than desired. If significant overcooling 
occurred, the RH could be low enough to activate the humidifier.
NOTE
Using SCR in Standard mode in conjunction with variable cooling capacity (e.g., chilled water 
valve or digital compressor) provides ultimate capacity control and energy-efficiency gains.
Temp Setpoint : 70°F
Proportional Band : 8°F
Deadband : 0°F
Cool 2
On
Cool 1
On
Cool 2
Off
Cool 1  Off
SCR Off
SCR
On
0%
100 %
Cooling
-100%
Heating
74
71
72
73
66
67
68
69
70
½ Proportional Band
Cooling 1 On
Cooling 2 On
½ Proportional Band
SCR On