Emerson Liebert iCOM Manual De Usuario
Operation
Liebert
®
iCOM
®
52
Compensated—The actual return air humidity sensor reading is sent to the Temperature and
Humidity Control where the Humidity Setpoint is adjusted based on how much the return room air
temperature deviates from the temperature setpoint. The adjusted humidity setpoint is used for
humidification percent requirement determination. For every 1°C deviation from the temperature
setpoint, the humidity setpoint is changed by 3% RH, inversely proportionally: if the temperature
increases, the humidity setpoint is decreased, and vice versa. The recalculated humidity setpoint is
shown as the Actual Humidity Setpoint (User Menu, Sensor Data). As the humidity setpoint is
automatically adjusted, the high and low humidity setpoints (User Menu, Set Alarms) are adjusted
accordingly. The unadjusted humidity sensor reading is displayed on the Status menu.
Predictive—The actual return air humidity sensor reading is adjusted before it is sent to the
Predictive—The actual return air humidity sensor reading is adjusted before it is sent to the
Temperature and Humidity Control. The humidity sensor reading is adjusted based on how much the
return room air temperature deviates from the desired temperature setpoint. For every 1°C deviation
from the temperature setpoint, the humidity sensor reading is changed by 3% RH, directly
proportionally: if the temperature increases, the humidity reading is increased and vice versa. The
adjusted humidity sensor reading is displayed in the Status menu. Predictive humidity control is set
at the factory as the default.
If Compensated or Predictive humidity sensor control is selected, overdehumidification is avoided.
If Compensated or Predictive humidity sensor control is selected, overdehumidification is avoided.
When overcooling occurs, causing an increase in the relative humidity sensor reading, the humidity
control program predicts what the RH will be when the dehumidification cycle ends and return air
temperature returns to the setpoint. This allows the dehumidification cycle to end at the proper time.
The Compensated and Predictive humidity sensor control can reduce energy consumption by
minimizing compressor and reheat operation, and eliminating unnecessary humidifier operation.
Humidity Control Types
The Liebert iCOM has two Humidity Control Types:
The Liebert iCOM has two Humidity Control Types:
• Proportional
• PI
• PI
Proportional—The control uses the humidity proportional band to determine whether to humidify
or to dehumidify and how much capacity to provide. The Humidity Proportional Band is a
user-defined range divided into two equal parts for humidifying and dehumidifying. The Humidity
Setpoint is located between these two equal parts. An optional Humidity Deadband range can be
defined, which is equally divided on either side of the setpoint and separates the two halves of the
proportional band. Figure 45 illustrates how the humidity proportional band is evenly divided on
either side of the humidity setpoint, with and without a deadband.
Figure 45 Humidity proportional band
NOTE
The historical humidity sensor graphs will display the real (unadjusted) sensor readings, no
The historical humidity sensor graphs will display the real (unadjusted) sensor readings, no
matter which Humidity Control Sensor Type is selected. The graphical sensor data is in the
User menu under Graphics.
0%
Setpoint
0%
+ 100%
Dehumidification
Dead-
band
Humidification
- Hum
+ Hum
0%
Setpoint
½ Proportional Band
Dehumidification
- 100%
Humidification
- 100%
humidification
Without Deadband
With Deadband
Humidification
- Hum
+ 100%
Dehumidification
+ Hum
Dehumidification
½ Proportional Band
½ Proportional Band
½ Proportional Band